The Circuit Breaker, cataloged under National Stock Number 5925-00-236-9000, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Federal Specifications Promulgated by General Services Administration Washington DC. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 4 commercial cross-references from 2 manufacturers, enabling identification through both NSN and commercial part number lookups. 11 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-236-9000 |
| Primary Part Number | WC375/18-004 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — No Item Name Available |
| Manufacturer | Federal Specifications Promulgated by General Services Administration Washington DC |
| Status | ACTIVE |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Test Data Document | 81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 14000.0 AC ALL LOCATIONS |
| Body Width | 4.125 INCHES NOMINAL IN |
| Reset Method | MANUAL |
| Specification/standard Data | 81348-W-C-375/18 GOVERNMENT SPECIFICATION |
| Actuator Function | TRIP-RESET |
| Trip Release Ambient Temp Rating | 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC |
| Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
| Maximum Continuous Load Current Rating Per Pole | 25.0 AMPERES AC ALL LOCATIONS |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 135.0 ALL LOCATIONS |
| Actuator Position Designation | AT POLE TWO |
| Terminal Type and Quantity | 6 COMPRESSION |
| Material | PLASTIC CASE |
| Pole Quantity | 3 |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 1.000 INCHES NOMINAL IN |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 4.000 INCHES NOMINAL IN |
| Center to Center Distance Between Terminals Parallel to Width | 1.000 INCHES NOMINAL IN |
| Special Handling Feature | MAGNETIC |
| Boss Height | 0.125 INCHES NOMINAL IN |
| Fragility Factor | MODERATELY RUGGED |
| Unthreaded Mounting Hole Diameter | 0.188 INCHES NOMINAL IN |
| Center to Center Distance Between Terminals Parallel to Length | 4.500 INCHES NOMINAL IN |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Mounting Facility Type and Quantity | 4 UNTHREADED HOLE(S) |
| Inclosure Protection Type for Which Designed | CORROSION RESISTANT |
| Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Acquisition Status | ACTIVE |
| HAZMAT | No |
| Part Number | Manufacturer |
|---|---|
| WC375/18-004 | Federal Specifications Promulgated by General Services Administration Washington DC (USA) |
| W-C-375/18 | Federal Specifications Promulgated by General Services Administration Washington DC (USA) |
| W-C-375/28-004 | Federal Specifications Promulgated by General Services Administration Washington DC (USA) |
| EHB3025 | Eaton Corporation Dba Eaton Inoac (USA) |
NSN 5925-00-236-9000 is a Circuit Breaker, manufactured by Federal Specifications Promulgated by General Services Administration Washington DC, classified under FSC 5925 (No Item Name Available). Status: active.
NSN 5925-00-236-9000 has 4 cross-referenced part numbers: WC375/18-004 (Federal Specifications Promulgated by General Services Administration Washington DC), W-C-375/18 (Federal Specifications Promulgated by General Services Administration Washington DC), W-C-375/28-004 (Federal Specifications Promulgated by General Services Administration Washington DC), EHB3025 (Eaton Corporation Dba Eaton Inoac).
There are 11 known substitutes for 5925-00-236-9000: 5925-00-211-1900, 5925-00-232-2840, 5925-00-433-1966 and 8 more. Verify interchangeability with system specifications before substitution.
Key specifications for WC375/18-004: Circuit Protection Type: OVERCURRENT ALL LOCATIONS; Test Data Document: 81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).; Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps: 14000.0 AC ALL LOCATIONS; Body Width: 4.125 INCHES NOMINAL IN. 30 total characteristics are documented in the Federal Logistics Information System.