PartsTable TECHNICAL DATA SHEET
JULY 2026Technical Data Sheet

W-C-375/18Circuit Breaker

Federal Specifications Promulgated by General Services Administration Washington DC · NSN 5925-00-232-2840 · FSC 5925 · No Item Name Available
Verified by PartsTable
NSN 5925-00-232-2840 — this item is cataloged by the U.S. Government under National Stock Number 5925-00-232-2840. Primary manufacturer part number: W-C-375/18.
Features
  • Circuit Breaker — FSC 5925
  • Trip Release Method: THERMAL-MAGNETIC ALL LOCATIONS
  • Circuit Protection Type: OVERCURRENT ALL LOCATIONS
  • Material: PLASTIC CASE
  • Main Contact Tripping Mechanism Type: TRIP FREE
  • Specification/standard Data: 81348-W-C-375/18 GOVERNMENT SPECIFICATION
  • Inclosure Protection Type for Which Designed: CORROSION RESISTANT
  • Trip Release Ambient Temp Rating: 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Applications
  • Applications requiring Plastic Case construction
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-232-2840, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Federal Specifications Promulgated by General Services Administration Washington DC. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 7 commercial cross-references from 3 manufacturers, enabling identification through both NSN and commercial part number lookups. 12 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-232-2840
Primary Part NumberW-C-375/18
Item NameCircuit Breaker
FSC / FSG5925 / 59 — No Item Name Available
ManufacturerFederal Specifications Promulgated by General Services Administration Washington DC
StatusACTIVE
Trip Release MethodTHERMAL-MAGNETIC ALL LOCATIONS
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
MaterialPLASTIC CASE
Main Contact Tripping Mechanism TypeTRIP FREE
Specification/standard Data81348-W-C-375/18 GOVERNMENT SPECIFICATION
Inclosure Protection Type for Which DesignedCORROSION RESISTANT
Trip Release Ambient Temp Rating40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Terminal Type and Quantity6 COMPRESSION
Trip Delay Time in Seconds Per Rated Continuous Current2.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Actuator FunctionTRIP-RESET
Maximum Continuous Load Current Rating Per Pole15.0 AMPERES AC ALL LOCATIONS
Frequency in Hertz60.0 ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Length4.000 INCHES NOMINAL IN
Boss Height0.125 INCHES NOMINAL IN
Unthreaded Mounting Hole Diameter0.188 INCHES NOMINAL IN
Mounting Facility Type and Quantity4 UNTHREADED HOLE(S)
Pole Quantity3
Center to Center Distance Between Terminals Parallel to Length4.500 INCHES NOMINAL IN
Special Handling FeatureMAGNETIC
Storage TypeGENERAL PURPOSE WAREHOUSE
Center to Center Distance Between Terminals Parallel to Width1.000 INCHES NOMINAL IN
Body Width4.125 INCHES NOMINAL IN
Distance Between Centerlines of Mounting Facilities Parallel to Body Width1.000 INCHES NOMINAL IN
Body Length6.000 INCHES NOMINAL IN
Manual Actuator Type and Quantity1 TOGGLE
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Actuator Position DesignationAT POLE TWO
Reset MethodMANUAL
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts480.0 AC ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
HAZMATNo
Verified Substitutes 12
5925-00-211-1900 INTERCHANGEABLE
Circuit Breaker
5925-00-236-9000 INTERCHANGEABLE
Circuit Breaker
5925-00-433-1966 INTERCHANGEABLE
Circuit Breaker
5925-00-443-4047 INTERCHANGEABLE
Circuit Breaker
5925-00-481-2093 INTERCHANGEABLE
Circuit Breaker
5925-01-041-5385EHD3015-A02J01 INTERCHANGEABLE
Circuit Breaker
Eaton Corporation Dba Eaton Inoac
5925-01-096-4663 INTERCHANGEABLE
Circuit Breaker
5925-01-096-4664 INTERCHANGEABLE
Circuit Breaker
5925-01-096-4697 INTERCHANGEABLE
Circuit Breaker
5925-01-128-4369 INTERCHANGEABLE
Circuit Breaker
Cross-Reference Index
Part NumberManufacturer
W-C-375/18 Federal Specifications Promulgated by General Services Administration Washington DC (USA)
4989D52G34 Eaton Corporation Dba Eaton Inoac (USA)
5925PL0935464 Jednolity Indeks Materialowy - Uniform Material Index (POL)
EHD3015 Eaton Corporation Dba Eaton Inoac (USA)
EHB3015 Eaton Corporation Dba Eaton Inoac (USA)
WC375/18-002 Federal Specifications Promulgated by General Services Administration Washington DC (USA)
EBH3015 Eaton Corporation Dba Eaton Inoac (USA)
Related Parts
5925-00-211-1900INTERCHANGEABLE
CIRCUIT BREAKER
5925-00-236-9000INTERCHANGEABLE
CIRCUIT BREAKER
5925-00-433-1966INTERCHANGEABLE
CIRCUIT BREAKER
5925-00-443-4047INTERCHANGEABLE
CIRCUIT BREAKER
5925-00-481-2093INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-041-5385INTERCHANGEABLE
CIRCUIT BREAKER
EHD3015-A02J01
5925-01-096-4663INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-096-4664INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-096-4697INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-128-4369INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-259-4726INTERCHANGEABLE
CIRCUIT BREAKER
5925-01-292-3301INTERCHANGEABLE
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-00-232-2840?

NSN 5925-00-232-2840 is a Circuit Breaker, manufactured by Federal Specifications Promulgated by General Services Administration Washington DC, classified under FSC 5925 (No Item Name Available). Status: active.

What are the part numbers for NSN 5925-00-232-2840?

NSN 5925-00-232-2840 has 7 cross-referenced part numbers: W-C-375/18 (Federal Specifications Promulgated by General Services Administration Washington DC), 4989D52G34 (Eaton Corporation Dba Eaton Inoac), 5925PL0935464 (Jednolity Indeks Materialowy - Uniform Material Index), EHD3015 (Eaton Corporation Dba Eaton Inoac), EHB3015 (Eaton Corporation Dba Eaton Inoac) and 2 more.

What NSN replaces 5925-00-232-2840?

There are 12 known substitutes for 5925-00-232-2840: 5925-00-211-1900, 5925-00-236-9000, 5925-00-433-1966 and 9 more. Verify interchangeability with system specifications before substitution.

What are the specifications of W-C-375/18?

Key specifications for W-C-375/18: Trip Release Method: THERMAL-MAGNETIC ALL LOCATIONS; Circuit Protection Type: OVERCURRENT ALL LOCATIONS; Material: PLASTIC CASE; Main Contact Tripping Mechanism Type: TRIP FREE. 30 total characteristics are documented in the Federal Logistics Information System.

Validated with multiple authoritative sources, including Government, OEM, and Certified sources.
PartsTable Design LLC · partstable.com