The CIRCUIT BREAKER is a the manufacturer industrial component. Key specifications include material: PLASTIC CASE, body_style: MULTIPOLE-SINGLE ACTUATOR TYPE, body_width: 1.937 INCHES MAXIMUM IN, body_height: 1.950 INCHES MAXIMUM IN, body_length: 1.562 INCHES MAXIMUM IN, reset_method: MANUAL. This part is cataloged in the Federal Logistics Information System under NSN 5925-00-421-2802, indicating validated use in U.S.
government and defense logistics supply chains. Available through authorized enterprise resellers and TPM (Third Party Maintenance) channels. Verify compatibility with your specific system configuration before ordering.
| material | PLASTIC CASE |
| body_style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| body_width | 1.937 INCHES MAXIMUM IN |
| body_height | 1.950 INCHES MAXIMUM IN |
| body_length | 1.562 INCHES MAXIMUM IN |
| reset_method | MANUAL |
| storage_type | GENERAL PURPOSE WAREHOUSE |
| pole_quantity | 3 |
| bushing_length | 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM IN |
| fragility_factor | MODERATELY RUGGED |
| special_features | FREQUESNCY: MAXIMUM AT 60 HZ AND 400 HZ; |
| actuator_function | TRIP-RESET |
| NSN | 5925-00-421-2802 |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| NOMINAL THREAD SIZE | 0.375 INCHES IN |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS |
| MAXIMUM INTERRUPTING CAPACITY CURRENT TYPE AND RATING PER POLE IN AMPS | 300.0 AC AND 500.0 DC ALL LOCATIONS |
| RESET METHOD | MANUAL |
| CIRCUIT PROTECTION TYPE | OVERCURRENT ALL LOCATIONS |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| INTERNAL TRIP RELEASE CONFIGURATION | SERIES TRIP ALL LOCATIONS |
| INCLOSURE PROTECTION TYPE FOR WHICH DESIGNED | HERMETICALLY SEALED AND MOISTURE RESISTANT AND VIBRATION RESISTANT AND FUNGUS RESISTANT AND SHOCK RESISTANT AND SALT SPRAY PROOF |
| ULTIMATE TRIP RATING OF CONTINUOUS CURRENT RATING PER POLE IN PERCENT | 115.0 ALL LOCATIONS |