This product is part of the Back-UPS range. The BK550EI features a total of 6 power outlets, 3 of which are UPS battery backup and 3 that are surge only. Its runtime at 100W is 24 minutes 20 seconds It provides data line protection with a RJ45 analog phone line for phone or fax or modem or DSL.
Its dimensions are 16.5 x 9.1 x 28.4 cm and 6.32kg. The BK550EI ensures office systems and their valuable data are protected from dangerous power surges, spikes and blackouts. This part is cataloged in the Federal Logistics Information System (FLIS) under NSN 6130-01-465-1969, indicating validated use in U.S.
government and defense logistics supply chains.
| input_phase | SINGLE SINGLE OPERATING POWER RQMT |
| output_phase | SINGLE MULTIPLE POWER OUTPUTS W/IDENTICAL RATINGS |
| overall_width | 91.0 MILLIMETERS NOMINAL MM |
| overall_height | 165.0 MILLIMETERS NOMINAL MM |
| overall_length | 330.0 MILLIMETERS NOMINAL MM |
| battery_location | INTERNAL |
| special_features | SHIPPING WEIGHT 7.05 KG,COLOR WHITE,BATTERY TYPE MAINTENANCE-FREE, SEALED LEAD-ACID BATTERY, LEAK PROOF,BATTERY SIZE 12 VOLT, 7AH,INPUT/OUTPUT VOLTAGE 230 V V |
| features_provided | BATTERY CHARGER AND CALIBRATED OUTPUT SIGNAL AND CIRCUIT BREAKER AND CIRCUIT OVERLOAD PROTECTION DEVICE AND EMI FILTER AND INPUT VOLTAGE RANGE SWITCH AND OVER CURRENT PROTECTOR AND VOLTAGE ADJUSTMENT |
| installation_design | TABLE |
| output_control_type | CURRENT LIMIT AND VOLTAGE ADJUSTMENT MULTIPLE POWER OUTPUTS W/IDENTICAL RATINGS |
| input_voltage_rating | 240.0 AC VOLTS MAXIMUM SINGLE OPERATING POWER RQMT |
| battery_recovery_time | 300.0 |
| NSN | 6130-01-465-1969 |
| OVERALL LENGTH | 330.0 MILLIMETERS NOMINAL MM |
| INSTALLATION DESIGN | BENCH |
| ELECTRICAL POWER SOURCE RELATIONSHIP | OPERATING |
| MAXIMUM OPERATING ALTITUDE RATING | 3000.0 METERS |
| FREQUENCY REGULATION PERCENT | 0.5 MULTIPLE POWER OUTPUTS W/IDENTICAL RATINGS |
| SPECIAL FEATURES | INPUT VOLTAGE ADJUSTABLE IN FIVE INCREMENTS FROM A HIGH OF 220.0 TO 240.0 VAC, GREATER THAN 196.0 VAC, GREATER THAN 184.0 VAC, GREATER THAN 172.0 VAC, TO A LOW OF 160.0 VAC TO COMPENSA TE FOR BROWNOUT CONDITIONS; INPUT LINEUSES AN IEC 320 MALE APPLIANCE COUPLER; OPTION SWITCHES ALLOW FOR CUSTOMIZATION OF TRANSFER VOLTAGE (ON BATTERY) IN A STEPPED APPROXIMATION TO SINE WAVE AT 225.0 VAC PLUS OR MINUS 5 PERCENT, SET ALARM, AND CONTROL OUTPUT FREQUENCY SETTINGS; UNIT HAS 4 IEC FEMALE APPLIANCE COUPLERS; AMBIENT OPERATING HUMIDITY PLUS 0.0 TO 95.0 PERCENT (NON-CONDENSING); HOT SWAPPABLE USER-REPLACEABLE BATTERIES; WEIGHS 7.0 KG; LOW VOLTAGE DIRECTIVE 73/23/EEC, GS LICENSES BY VDE PER STANDARD EN60950 AND EN50091; EMC DIRECTIVE 89/336/EEC, C-TICK APPROVED, EN5022 (CISPR22) AND EN50082-1 VAC |
| FEATURES PROVIDED | BATTERY CHARGER AND CALIBRATED OUTPUT SIGNAL AND CIRCUIT BREAKER AND CIRCUIT OVERLOAD PROTECTION DEVICE AND EMI FILTER AND INPUT VOLTAGE RANGE SWITCH AND OVER CURRENT PROTECTOR AND VOLTAGE ADJUSTMENT |
| OUTPUT CONNECTION QUANTITY | 4 MULTIPLE POWER OUTPUTS W/IDENTICAL RATINGS |
| BATTERY FEATURE AND TYPE | RECHARGEABLE LEAD ACID CELL |
| POWER SUPPLIES PROGRAMMED PER SYSTEM | 4 |