PartsTable TECHNICAL DATA SHEET
NSN 5925-01-693-6852Government record, cited

Circuit Breaker5925-01-693-6852

NSN 5925-01-693-6852 · NIIN 016936852
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-693-6852 · 5925016936852 · NIIN 016936852 · 01-693-6852 · FSC 5925 Circuit Breakers
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Bushing Length: 0.495 INCHES NOMINAL IN
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP W/AUXILIARY LOAD TERMINAL SINGLE LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 80.0 DC SINGLE LOCATION
  • Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S)
  • Actuator Position Designation: AT POLE ONE
  • Ultimate Trip Time Per Pole in Seconds: 0.006 MINIMUM AND 0.1 MAXIMUM SINGLE LOCATION
Identification
  • NSN: 5925-01-693-6852
  • NIIN: 016936852
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-693-6852, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 28 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-693-6852
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Bushing Length0.495 INCHES NOMINAL IN
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP W/AUXILIARY LOAD TERMINAL SINGLE LOCATION
Operating Voltage Type and Rating Per Pole in Volts80.0 DC SINGLE LOCATION
Mounting Facility Type and Quantity2 UNTHREADED HOLE(S)
Actuator Position DesignationAT POLE ONE
Ultimate Trip Time Per Pole in Seconds0.006 MINIMUM AND 0.1 MAXIMUM SINGLE LOCATION
Frequency in Hertz60 SINGLE LOCATION
Body StyleSINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent1000.0 SINGLE LOCATION
Distance Between Centerlines of Mounting Facilities Parallel to Body Length0.656 INCHES NOMINAL IN
Circuit Protection TypeOVERCURRENT SINGLE LOCATION
Body Width0.750 INCHES NOMINAL IN
Unthreaded Mounting Hole Diameter0.156 INCHES NOMINAL IN
Pole Quantity1
Mounting Surface to Terminal End Distance2.256 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole15.0 AMPERES DC SINGLE LOCATION
Trip Release CharacteristicTIME DELAY SINGLE LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps50.0 DC SINGLE LOCATION
Body Length2.00 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current2.0 MINIMUM AT 125 PCT AND 60.0 MAXIMUM AT 125 PCT SINGLE LOCATION
Manual Actuator Type and Quantity1 TOGGLE
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity5 QUICK DISCONNECT, MALE
Main Contact Tripping Mechanism TypeTRIP FREE
Trip Release MethodMAGNETIC SINGLE LOCATION
Auxiliary Switch Function and Quantity1 CONTROL
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
IUGN6-1REC4-52-15.0-A 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-693-6852?

NSN 5925-01-693-6852 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-693-6852?

Key specifications for 5925-01-693-6852: Bushing Length: 0.495 INCHES NOMINAL IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP W/AUXILIARY LOAD TERMINAL SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 80.0 DC SINGLE LOCATION. 28 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-693-6852 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.