PartsTable TECHNICAL DATA SHEET
NSN 5925-01-529-3547Government record, cited

Circuit Breaker5925-01-529-3547

NSN 5925-01-529-3547 · NIIN 015293547 · Part number W92X112-50
Tyco Electronics Corp · FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components · CAGE 0BKV9
Government record, cited
NSN 5925-01-529-3547 — this item is cataloged by the U.S. Government under National Stock Number 5925-01-529-3547. Manufacturer of record part number: W92X112-50.
Also searched as  5925-01-529-3547 · 5925015293547 · NIIN 015293547 · 01-529-3547 · FSC 5925 Circuit Breakers · CAGE 0BKV9 · W92X112-50
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: AUTOMATIC
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 277.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 4 THREADED HOLE(S)
  • Frequency in Hertz: 50.0 OR 60.0 ALL LOCATIONS
  • Center to Center Distance Between Terminals Parallel to Width: 0.938 INCHES NOMINAL IN
  • Body Style: MULTIPOLE-SINGLE ACTUATOR TYPE
Identification
  • NSN: 5925-01-529-3547
  • NIIN: 015293547
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
  • Primary part number: W92X112-50
  • Manufacturer: Tyco Electronics Corp
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-529-3547, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is Tyco Electronics Corp. Government technical data includes 28 specifications, cited from the U.S. Government catalog. The record lists 1 manufacturer part number for this item, enabling identification through both NSN and commercial part number lookups. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-529-3547
Primary Part NumberW92X112-50
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
ManufacturerTyco Electronics Corp
StatusACTIVE
Reset MethodAUTOMATIC
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts277.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity4 THREADED HOLE(S)
Frequency in Hertz50.0 OR 60.0 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width0.938 INCHES NOMINAL IN
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Length2.065 INCHES NOMINAL IN
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width1.500 INCHES NOMINAL IN
Pole Quantity2
Mounting Surface to Terminal End Distance2.500 INCHES NOMINAL IN
Maximum Continuous Load Current Rating Per Pole50.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC ALL LOCATIONS
Nominal Thread Size0.138 INCHES IN
Body Length2.500 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current2.200 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity2 TOGGLE
Distance Between Centerlines of Mounting Facilities Parallel to Body Width0.750 INCHES NOMINAL IN
Inclosure Protection Type for Which DesignedMOISTURE RESISTANT AND FUNGUS RESISTANT
Thread Quantity Per Inch32
Terminal Type and Quantity4 THREADED STUD
Thread Series DesignatorUNIFIED NATIONAL COARSE (UNC)
Boss Height0.140 INCHES NOMINAL IN
Trip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Length1.940 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
Part NumberManufacturer
W92X112-50 PRIMARY Tyco Electronics Corp (USA)

Frequently Asked Questions

What is NSN 5925-01-529-3547?

NSN 5925-01-529-3547 is a Circuit Breaker, manufactured by Tyco Electronics Corp, classified under FSC 5925, Circuit Breakers. Status: active.

What part numbers are listed for NSN 5925-01-529-3547?

NSN 5925-01-529-3547 has 1 manufacturer part number on file: W92X112-50 (Tyco Electronics Corp).

What are the specifications of W92X112-50?

Key specifications for W92X112-50: Reset Method: AUTOMATIC; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 277.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 THREADED HOLE(S). 28 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-529-3547 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com