The Circuit Breaker, cataloged under National Stock Number 5925-01-469-6667, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 28 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-469-6667 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 120.0 AC AND 250.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 2 CLIP |
| Frequency in Hertz | 50.0 OR 60.0 ALL LOCATIONS |
| Center to Center Distance Between Terminals Parallel to Width | 0.825 INCHES NOMINAL IN |
| Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| Switch Voltage Rating and Type in Volts | 250.0 AC AND 28.0 DC |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 800.0 ALL LOCATIONS |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 1.325 INCHES NOMINAL IN |
| Body Height | 1.770 INCHES NOMINAL IN |
| Pole Quantity | 2 |
| Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 50.0 AC ALL LOCATIONS |
| Body Length | 2.000 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.019 MINIMUM AT 600 PCT AND 0.150 MAXIMUM AT 600 PCT FOURTH LOCATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.040 MINIMUM AT 400 PCT AND 0.500 MAXIMUM AT 400 PCT THIRD LOCATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.100 MAXIMUM AT 800 PCT FIFTH LOCATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.200 MINIMUM AT 200 PCT AND 1.700 MAXIMUM AT 200 PCT SECOND LOCATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.900 MINIMUM AT 125 PCT AND 10.000 MAXIMUM AT 125 PCT FIRST LOCATION |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Material | PLASTIC CASE |
| Terminal Type and Quantity | 4 QUICK DISCONNECT, MALE |
| Main Contact Tripping Mechanism Type | NONTRIP FREE |
| Boss Height | 0.250 INCHES NOMINAL IN |
| Trip Release Method | MAGNETIC ALL LOCATIONS |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| 203-22-1-64-502-4-2-1 | 3/2 Design control — primary reference U.S. Government activity |
NSN 5925-01-469-6667 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-469-6667: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC AND 250.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 2 CLIP. 28 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.