PartsTable TECHNICAL DATA SHEET
NSN 5925-01-413-5679Government record, cited

Circuit Breaker5925-01-413-5679

NSN 5925-01-413-5679 · NIIN 014135679
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-413-5679 · 5925014135679 · NIIN 014135679 · 01-413-5679 · FSC 5925 Circuit Breakers · MIL-PRF-55629/1 · M55629/1-365 · MIL-C-55629B
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 50.0 DC SINGLE LOCATION
  • Mounting Facility Type and Quantity: 2 THREADED HOLE(S)
  • Frequency in Hertz: 400.0 SINGLE LOCATION
  • Body Style: SINGLE POLE TYPE
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 200.0 SINGLE LOCATION
Identification
  • NSN: 5925-01-413-5679
  • NIIN: 014135679
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-413-5679, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 27 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 2 items share a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-413-5679
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP SINGLE LOCATION
Operating Voltage Type and Rating Per Pole in Volts240.0 AC AND 50.0 DC SINGLE LOCATION
Mounting Facility Type and Quantity2 THREADED HOLE(S)
Frequency in Hertz400.0 SINGLE LOCATION
Body StyleSINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent200.0 SINGLE LOCATION
Distance Between Centerlines of Mounting Facilities Parallel to Body Length2.062 INCHES NOMINAL IN
Circuit Protection TypeOVERCURRENT SINGLE LOCATION
Body Width0.755 INCHES NOMINAL IN
Pole Quantity1
Mounting Surface to Terminal End Distance2.800 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole10.0 AMPERES AC SINGLE LOCATION
Trip Release CharacteristicTIME DELAY SINGLE LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps1000.0 AC SINGLE LOCATION
Nominal Thread Size2.138 INCHES IN
Specification/standard Data81349--55629/1-365 GOVERNMENT SPECIFICATION
Body Length2.510 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current20.000 MAXIMUM AT 200 PCT AND 3.000 MINIMUM AT 200 PCT SINGLE LOCATION
Test Data Document81349-MILC55629B SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
MaterialPLASTIC CASE
Terminal Type and Quantity2 THREADED STUD
Main Contact Tripping Mechanism TypeTRIP FREE
Thread Series DesignatorUNIFIED NATIONAL COARSE (UNC)
Boss Height2.340 INCHES MAXIMUM IN
Trip Release MethodMAGNETIC SINGLE LOCATION
Center to Center Distance Between Terminals Parallel to Length1.810 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
⇄ Related Items 2
Each row states its source: a government interchangeability/replacement code, or a possible match on a shared part number.
5925-01-414-9143 POSSIBLE MATCH
CIRCUIT BREAKER
Possible match (shared part number)
5925-01-468-6257 POSSIBLE MATCH
CIRCUIT BREAKER
Possible match (shared part number)
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
MIL-PRF-55629/1 4/1 Identification reference
U.S. Government activity
M55629/1-365 2/2 Government specification standardization
U.S. Government activity
MIL-C-55629B 5/9 Secondary reference
U.S. Government activity
Related Parts
5925-01-414-9143POSSIBLE MATCH
CIRCUIT BREAKER
5925-01-468-6257POSSIBLE MATCH
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-413-5679?

NSN 5925-01-413-5679 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What NSN replaces 5925-01-413-5679?

2 possible matches (shared part number, not a government interchangeability claim): 5925-01-414-9143, 5925-01-468-6257. Verify interchangeability with system specifications before substitution.

What are the specifications of 5925-01-413-5679?

Key specifications for 5925-01-413-5679: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 50.0 DC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 27 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-413-5679 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com