PartsTable TECHNICAL DATA SHEET
NSN 5925-01-359-4080Government record, cited

Circuit Breaker5925-01-359-4080

NSN 5925-01-359-4080 · NIIN 013594080
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-359-4080 · 5925013594080 · NIIN 013594080 · 01-359-4080 · FSC 5925 Circuit Breakers · M39019/03-342 · MIL-PRF-39019/3 · MIL-C-39019/3 · MIL-PRF-39017
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Bushing Length: 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM IN
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 50.0 DC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 1 THREADED BUSHING WITH PANEL SEAL
  • Actuator Position Designation: BETWEEN POLE ONE AND TWO
  • Frequency in Hertz: 60.0 OR 400.0 ALL LOCATIONS
Identification
  • NSN: 5925-01-359-4080
  • NIIN: 013594080
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-359-4080, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 27 specifications, cited from the U.S. Government catalog. 4 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 9 items share a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-359-4080
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Bushing Length0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM IN
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts240.0 AC AND 50.0 DC ALL LOCATIONS
Mounting Facility Type and Quantity1 THREADED BUSHING WITH PANEL SEAL
Actuator Position DesignationBETWEEN POLE ONE AND TWO
Frequency in Hertz60.0 OR 400.0 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width0.625 INCHES NOMINAL IN
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent200.0 ALL LOCATIONS
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width1.281 INCHES MAXIMUM IN
Pole Quantity2
Mounting Surface to Terminal End Distance1.828 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole1.5 AMPERES AC AND 1.5 AMPERES DC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps300.0 AC AND 500.0 DC ALL LOCATIONS
Nominal Thread Size0.375 INCHES IN
Body Length1.562 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current0.055 MINIMUM AT 200 PCT AND 0.950 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity4 WIRE HOOK
Main Contact Tripping Mechanism TypeTRIP FREE
Thread Series DesignatorUNEF
Trip Release MethodMAGNETIC ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Length0.906 INCHES MAXIMUM IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
⇄ Related Items 9
Each row states its source: a government interchangeability/replacement code, or a possible match on a shared part number.
5905-01-372-9909 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-463-4853 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-533-6144 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-560-7480 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-596-5768 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-611-2002RLR32C1000GRR64 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)Vishay Dale Electronics, Llc Div Vishay Americas
5905-01-644-0523RLR07C4R75FS POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)Vishay Americas
5905-01-681-4826 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
5905-01-681-5103 POSSIBLE MATCH
RESISTOR,FIXED,FILM
Possible match (shared part number)
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
M39019/03-342 2/2 Government specification standardization
U.S. Government activity
MIL-PRF-39019/3 4/1 Identification reference
U.S. Government activity
MIL-C-39019/3 5/9 Secondary reference
U.S. Government activity
MIL-PRF-39017 5/9 Secondary reference
U.S. Government activity
Related Parts
5905-01-372-9909POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-463-4853POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-533-6144POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-560-7480POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-596-5768POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-611-2002POSSIBLE MATCH
RESISTOR,FIXED,FILM
RLR32C1000GRR64
5905-01-644-0523POSSIBLE MATCH
RESISTOR,FIXED,FILM
RLR07C4R75FS
5905-01-681-4826POSSIBLE MATCH
RESISTOR,FIXED,FILM
5905-01-681-5103POSSIBLE MATCH
RESISTOR,FIXED,FILM

Frequently Asked Questions

What is NSN 5925-01-359-4080?

NSN 5925-01-359-4080 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What NSN replaces 5925-01-359-4080?

9 possible matches (shared part number, not a government interchangeability claim): 5905-01-372-9909, 5905-01-463-4853, 5905-01-533-6144. Verify interchangeability with system specifications before substitution.

What are the specifications of 5925-01-359-4080?

Key specifications for 5925-01-359-4080: Bushing Length: 0.332 INCHES MINIMUM AND 0.380 INCHES MAXIMUM IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 50.0 DC ALL LOCATIONS. 27 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-359-4080 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com