PartsTable TECHNICAL DATA SHEET
NSN 5925-01-345-4976Government record, cited

Circuit Breaker5925-01-345-4976

NSN 5925-01-345-4976 · NIIN 013454976
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-345-4976 · 5925013454976 · NIIN 013454976 · 01-345-4976 · FSC 5925 Circuit Breakers · HFD2060L · 100-001532 · HFD2060
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 600.0 AC AND 250.0 DC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 4 UNTHREADED HOLE(S)
  • Actuator Position Designation: BETWEEN POLE ONE AND TWO
  • Frequency in Hertz: 60.0 ALL LOCATIONS
  • Fragility Factor: MODERATELY RUGGED
Identification
  • NSN: 5925-01-345-4976
  • NIIN: 013454976
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-345-4976, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 25 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-345-4976
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts600.0 AC AND 250.0 DC ALL LOCATIONS
Mounting Facility Type and Quantity4 UNTHREADED HOLE(S)
Actuator Position DesignationBETWEEN POLE ONE AND TWO
Frequency in Hertz60.0 ALL LOCATIONS
Fragility FactorMODERATELY RUGGED
Body StyleRECTANGULAR DIMENSIONAL ENVELOPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Storage TypeGENERAL PURPOSE WAREHOUSE
Unthreaded Mounting Hole Diameter0.196 INCHES NOMINAL IN
Pole Quantity2
Maximum Continuous Load Current Rating Per Pole60.0 AMPERES AC AND 60.0 AMPERES DC ALL LOCATIONS
Trip Release CharacteristicINSTANTANEOUS ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps25000.0 AC AND 22000.0 DC ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedDUSTPROOF AND FUNGUS PROOF
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity6 COMPRESSION
Special Handling FeatureMAGNETIC
Main Contact Tripping Mechanism TypeTRIP FREE
Trip Release MethodMAGNETIC ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
HFD2060L 3/2 Design control — primary reference
U.S. Government activity
100-001532 5/9 Secondary reference
International Switchboard Corp Div of Equus Power Systems Corp
HFD2060 C/1 Advisory reference — outside the item-of-supply concept
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-345-4976?

NSN 5925-01-345-4976 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-345-4976?

Key specifications for 5925-01-345-4976: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 600.0 AC AND 250.0 DC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 UNTHREADED HOLE(S). 25 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-345-4976 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com