PartsTable TECHNICAL DATA SHEET
NSN 5925-01-331-8636Government record, cited

Circuit Breaker5925-01-331-8636

NSN 5925-01-331-8636 · NIIN 013318636
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-331-8636 · 5925013318636 · NIIN 013318636 · 01-331-8636 · FSC 5925 Circuit Breakers · AQBA50 · 7908947-14 · MIL-C-17361AQB-A50,5 · MIL-C-17361/1 · MIL-DTL-17361/1
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 500.0 AC AND 250.0 DC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 2 THREADED HOLE(S)
  • Actuator Position Designation: AT POLE TWO
  • Frequency in Hertz: 60.00 ALL LOCATIONS
  • Center to Center Distance Between Terminals Parallel to Width: 1.125 INCHES NOMINAL IN
  • Fragility Factor: MODERATELY RUGGED
Identification
  • NSN: 5925-01-331-8636
  • NIIN: 013318636
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-331-8636, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 8 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-331-8636
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts500.0 AC AND 250.0 DC ALL LOCATIONS
Mounting Facility Type and Quantity2 THREADED HOLE(S)
Actuator Position DesignationAT POLE TWO
Frequency in Hertz60.00 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width1.125 INCHES NOMINAL IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent138.0 ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Length0.625 INCHES NOMINAL IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width3.344 INCHES NOMINAL IN
Body Height3.375 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity3
Maximum Continuous Load Current Rating Per Pole50.0 AMPERES AC AND 50.0 AMPERES DC ALL LOCATIONS
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC AND 2500.0 DC ALL LOCATIONS
Nominal Thread Size0.216 INCHES IN
Specification/standard Data81349-MIL-C-17361 GOVERNMENT SPECIFICATION
Body Length4.125 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current10.000 MINIMUM AT 200 PCT AND 200.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Distance Between Centerlines of Mounting Facilities Parallel to Body Width2.938 INCHES NOMINAL IN
Inclosure Protection Type for Which DesignedSHOCK RESISTANT AND VIBRATION RESISTANT
Test Data Document81349-MIL-C-17361 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
Thread Quantity Per Inch24
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
AQBA50 5/9 Secondary reference
U.S. Government activity
7908947-14 C/1 Advisory reference — outside the item-of-supply concept
U.S. Government activity
MIL-C-17361AQB-A50,5 C/1 Advisory reference — outside the item-of-supply concept
U.S. Government activity
MIL-C-17361/1 5/9 Secondary reference
U.S. Government activity
MIL-DTL-17361/1 4/1 Identification reference
U.S. Government activity
AQB-A50-50 2/2 Government specification standardization
U.S. Government activity
M1LC17361TYPQBA50 C/1 Advisory reference — outside the item-of-supply concept
U.S. Government activity
3203134-P14 C/1 Advisory reference — outside the item-of-supply concept
Naval Sea Systems Command

Frequently Asked Questions

What is NSN 5925-01-331-8636?

NSN 5925-01-331-8636 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-331-8636?

Key specifications for 5925-01-331-8636: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 500.0 AC AND 250.0 DC ALL LOCATIONS; Mounting Facility Type and Quantity: 2 THREADED HOLE(S); Actuator Position Designation: AT POLE TWO. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-331-8636 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com