PartsTable TECHNICAL DATA SHEET
NSN 5925-01-317-9966Government record, cited

Circuit Breaker5925-01-317-9966

NSN 5925-01-317-9966 · NIIN 013179966
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-317-9966 · 5925013179966 · NIIN 013179966 · 01-317-9966 · FSC 5925 Circuit Breakers
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Bushing Length: 0.495 INCHES NOMINAL IN
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP W/AUXILIARY LOAD TERMINAL ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 1 THREADED BUSHING WITH PANEL SEAL
  • Switch Terminal Type: QUICK DISCONNECT, MALE
  • Frequency in Hertz: 400.0 ALL LOCATIONS
Identification
  • NSN: 5925-01-317-9966
  • NIIN: 013179966
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-317-9966, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 28 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-317-9966
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Bushing Length0.495 INCHES NOMINAL IN
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP W/AUXILIARY LOAD TERMINAL ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts250.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity1 THREADED BUSHING WITH PANEL SEAL
Switch Terminal TypeQUICK DISCONNECT, MALE
Frequency in Hertz400.0 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width0.750 INCHES NOMINAL IN
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Switch Location and Position DesignationINTERNAL AT POLE ONE
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width1.500 INCHES NOMINAL IN
Pole Quantity2
Mounting Surface to Terminal End Distance2.200 INCHES NOMINAL IN
Maximum Continuous Load Current Rating Per Pole0.5 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Nominal Thread Size0.500 INCHES IN
Body Length2.000 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current0.500 MINIMUM AT 150 PCT AND 8.000 MAXIMUM AT 150 PCT AND 0.150 MINIMUM AT 200 PCT AND 1.900 MAXIMUM AT 200 PCT AND 0.020 MINIMUM AT 400 PCT AND 0.400 MAXIMUM AT 400 PCT AND 0.006 MINIMUM AT 600 PCT AND 0.250 MAXIMUM AT 600 PCT AND 0.004 MINIMUM AT 800 PCT AND 0.100 MAXIMUM AT 800 PCT AND 0.004 MINIMUM AT 1000 PCT AND 0.050 MAXIMUM AT 1000 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedMOISTURE RESISTANT AND CORROSION RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT
Thread Quantity Per Inch32
Terminal Type and Quantity10 QUICK DISCONNECT, MALE
Main Contact Tripping Mechanism TypeTRIP FREE
Thread Series DesignatorUN
Trip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
Auxiliary Switch Function and Quantity1 CONTROL
Center to Center Distance Between Terminals Parallel to Length1.530 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
APGN11-1REC4-41-501 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-317-9966?

NSN 5925-01-317-9966 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-317-9966?

Key specifications for 5925-01-317-9966: Bushing Length: 0.495 INCHES NOMINAL IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP W/AUXILIARY LOAD TERMINAL ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS. 28 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-317-9966 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com