The Circuit Breaker, cataloged under National Stock Number 5925-01-317-9963, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-317-9963 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Bushing Length | 0.625 INCHES NOMINAL IN |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 250.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 1 THREADED BUSHING WITH PANEL SEAL |
| Actuator Position Designation | AT POLE TWO |
| Switch Terminal Type | QUICK DISCONNECT, MALE |
| Frequency in Hertz | 50.0 OR 60.0 ALL LOCATIONS |
| Unpackaged Unit Weight | 9.000 OUNCES NOMINAL OZ |
| Center to Center Distance Between Terminals Parallel to Width | 0.750 INCHES NOMINAL IN |
| Nonturn Device Radius | 0.656 INCHES NOMINAL IN |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| Switch Voltage Rating and Type in Volts | 250.0 AC AND 30.0 DC |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 115.0 ALL LOCATIONS |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Switch Location and Position Designation | INTERNAL AT POLE ONE |
| Nonturn Device Length | 0.130 INCHES NOMINAL IN |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 2.250 INCHES NOMINAL IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 3 |
| Mounting Surface to Terminal End Distance | 2.200 INCHES MAXIMUM IN |
| Thread Pitch Diameters | +0.4752 TO 0.4787 INCHES IN |
| Maximum Continuous Load Current Rating Per Pole | 2.5 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 3500.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.500 INCHES IN |
| Body Length | 2.000 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 7.000 MINIMUM AT 125 PCT AND 90.000 MAXIMUM AT 125 PCT AND 3.000 MINIMUM AT 150 PCT AND 40.000 MAXIMUM AT 150 PCT AND 1.000 MINIMUM AT 200 PCT AND 12.000 MAXIMUM AT 200 PCT AND 0.200 MINIMUM AT 400 PCT AND 3.000 MAXIMUM AT 400 PCT AND 0.080 MINIMUM AT 600 PCT AND 1.000 MAXIMUM AT 600 PCT AND 0.030 MINIMUM AT 800 PCT AND 0.700 MAXIMUM AT 800 PCT AND 0.016 MINIMUM AT 1000 PCT AND 0.300 MAXIMUM AT 1000 PCT ALL LOCATIONS |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| APGN-111-1REC4-65F-252 | 3/2 Design control — primary reference U.S. Government activity |
NSN 5925-01-317-9963 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-317-9963: Bushing Length: 0.625 INCHES NOMINAL IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS. 30 specifications are documented in the U.S. Government catalog.