PartsTable TECHNICAL DATA SHEET
NSN 5925-01-281-1327Government record, cited

Circuit Breaker5925-01-281-1327

NSN 5925-01-281-1327 · NIIN 012811327
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-281-1327 · 5925012811327 · NIIN 012811327 · 01-281-1327 · FSC 5925 Circuit Breakers · TQC2110WL · P-7211
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 4 TERMINAL
  • Actuator Position Designation: AT EACH POLE
  • Frequency in Hertz: 60.0 ALL LOCATIONS
  • Center to Center Distance Between Terminals Parallel to Width: 1.000 INCHES NOMINAL IN
Identification
  • NSN: 5925-01-281-1327
  • NIIN: 012811327
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-281-1327, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 29 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-281-1327
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts240.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity4 TERMINAL
Actuator Position DesignationAT EACH POLE
Frequency in Hertz60.0 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width1.000 INCHES NOMINAL IN
Body StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent140.0 ALL LOCATIONS
External Actuator Linkage ArrangementONE AND TWO LINKED
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.000 INCHES MAXIMUM IN
Body Height2.359 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity2
Maximum Continuous Load Current Rating Per Pole10.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC ALL LOCATIONS
Body Length3.875 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current18.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity2 TOGGLE
Inclosure Protection Type for Which DesignedGENERAL PURPOSE
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Trip Release Ambient Temp Rating50.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Terminal Type and Quantity2 COMPRESSION AND 2 CLIP
Main Contact Tripping Mechanism TypeTRIP FREE
Boss Height0.187 INCHES NOMINAL IN
Trip Release MethodTHERMAL ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
TQC2110WL 5/9 Secondary reference
General Electric Co Outdoor Breaker Business Section
P-7211 3/9 Design control — primary reference
Stored Energy Systems, a Limited Liability Company Dba Stored Energy Systems a Llc

Frequently Asked Questions

What is NSN 5925-01-281-1327?

NSN 5925-01-281-1327 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-281-1327?

Key specifications for 5925-01-281-1327: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 TERMINAL. 29 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-281-1327 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com