Features
  • Circuit Breaker — FSC 5925
  • Bushing Length: 0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM IN
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC SECOND LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 50.0 DC FIRST LOCATION
  • Mounting Facility Type and Quantity: 1 THREADED BUSHING WITH PANEL SEAL1 THREADED BUSHING WITH PANEL SEAL
  • Actuator Position Designation: BETWEEN POLE ONE AND TWO
Identification
  • NSN: 5925-01-254-6590
  • NIIN: 012546590
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-254-6590, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-254-6590
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Bushing Length0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM IN
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts250.0 AC SECOND LOCATION
Operating Voltage Type and Rating Per Pole in Volts50.0 DC FIRST LOCATION
Mounting Facility Type and Quantity1 THREADED BUSHING WITH PANEL SEAL1 THREADED BUSHING WITH PANEL SEAL
Actuator Position DesignationBETWEEN POLE ONE AND TWO
Frequency in Hertz50.0 OR 60.0 SECOND LOCATION
Center to Center Distance Between Terminals Parallel to Width0.625 INCHES NOMINAL0.625 INCHES NOMINAL IN
Nonturn Device Radius0.625 INCHES NOMINAL0.625 INCHES NOMINAL IN
Fragility FactorMODERATELY RUGGEDMODERATELY RUGGED
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Arc Quenching MethodMAGNETIC BLOWOUTMAGNETIC BLOWOUT
Nonturn Device Length0.130 INCHES NOMINAL0.130 INCHES NOMINAL IN
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width1.250 INCHES MAXIMUM1.250 INCHES MAXIMUM IN
Storage TypeGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
Pole Quantity22
Mounting Surface to Terminal End Distance1.780 INCHES MAXIMUM1.780 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole1.0 AMPERES AC SECOND LOCATION
Maximum Continuous Load Current Rating Per Pole5.0 AMPERES DC FIRST LOCATION
Features ProvidedHIGH INRUSH PROTECTIONHIGH INRUSH PROTECTION
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps300.0 AC SECOND LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps500.0 DC FIRST LOCATION
Nominal Thread Size0.375 INCHES IN
Body Length1.500 INCHES MAXIMUM1.500 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current0.600 MINIMUM AT 200 PCT AND 6.000 MAXIMUM AT 200 PCT FIRST LOCATION
Trip Delay Time in Seconds Per Rated Continuous Current1.150 MINIMUM AT 200 PCT AND 7.000 MAXIMUM AT 200 PCT SECOND LOCATION
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
0N332775-1 7/2 Vendor item drawing reference
U.S. Government activity
AP-12-21074-1 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-254-6590?

NSN 5925-01-254-6590 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-254-6590?

Key specifications for 5925-01-254-6590: Bushing Length: 0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC SECOND LOCATION. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-254-6590 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com