The Circuit Breaker, cataloged under National Stock Number 5925-01-248-1384, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-248-1384 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Bushing Length | 0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM IN |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 240.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S)2 THREADED HOLE(S) |
| Actuator Position Designation | AT POLE ONE |
| Frequency in Hertz | 400.0 ALL LOCATIONS |
| Center to Center Distance Between Terminals Parallel to Width | 0.625 INCHES NOMINAL0.625 INCHES NOMINAL IN |
| Fragility Factor | MODERATELY RUGGEDMODERATELY RUGGED |
| Body Style | MULTIPOLE-SINGLE ACTUATOR TYPEMULTIPOLE-SINGLE ACTUATOR TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 115.0 ALL LOCATIONS |
| Arc Quenching Method | AIRAIR |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 1.875 INCHES MAXIMUM1.875 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 33 |
| Mounting Surface to Terminal End Distance | 2.160 INCHES MAXIMUM2.160 INCHES MAXIMUM IN |
| Thread Pitch Diameters | +0.1177 TO 0.1214 INCHES+0.1177 TO 0.1214 INCHES IN |
| Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 1.500 INCHES NOMINAL1.500 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.200 MINIMUM AT 200 PCT AND 6.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Inclosure Protection Type for Which Designed | HERMETICALLY SEALED |
| Thread Quantity Per Inch | 3232 |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Terminal Type and Quantity | 6 SOLDER STUD |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| 841003-3 | 3/2 Design control — primary reference U.S. Government activity |
| AP112-2408-3 | 5/2 Secondary reference U.S. Government activity |
NSN 5925-01-248-1384 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-248-1384: Bushing Length: 0.380 INCHES MAXIMUM0.380 INCHES MAXIMUM IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC ALL LOCATIONS. 30 specifications are documented in the U.S. Government catalog.