PartsTable TECHNICAL DATA SHEET
NSN 5925-01-229-8654Government record, cited

Circuit Breaker5925-01-229-8654

NSN 5925-01-229-8654 · NIIN 012298654 · Part number CD2-Z-406-1
Heinemann Electric Canada Incdivision of Eaton Corp · FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components · CAGE L3330
Government record, cited
NSN 5925-01-229-8654 — this item is cataloged by the U.S. Government under National Stock Number 5925-01-229-8654. Manufacturer of record part number: CD2-Z-406-1.
Also searched as  5925-01-229-8654 · 5925012298654 · NIIN 012298654 · 01-229-8654 · FSC 5925 Circuit Breakers · CAGE L3330 · CD2-Z-406-1 · CD2-A3A6-85-240-1-11 · CD2A3A9UP185A240AC12 · WT-C0078-001 · CD2A3A6U-P1-85A240AC1-P2-115AC-P
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP FIRST LOCATION
  • Internal Trip Release Configuration: RELAY TRIP SECOND LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC FIRST LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 115.0 AC SECOND LOCATION
  • Mounting Facility Type and Quantity: 4 THREADED HOLE(S) AND 4 SLOT
  • Actuator Position Designation: AT EACH POLE
Identification
  • NSN: 5925-01-229-8654
  • NIIN: 012298654
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
  • Primary part number: CD2-Z-406-1
  • Manufacturer: Heinemann Electric Canada Incdivision of Eaton Corp
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-229-8654, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is Heinemann Electric Canada Incdivision of Eaton Corp. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 1 manufacturer part number for this item, enabling identification through both NSN and commercial part number lookups. 5 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-229-8654
Primary Part NumberCD2-Z-406-1
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
ManufacturerHeinemann Electric Canada Incdivision of Eaton Corp
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP FIRST LOCATION
Internal Trip Release ConfigurationRELAY TRIP SECOND LOCATION
Operating Voltage Type and Rating Per Pole in Volts240.0 AC FIRST LOCATION
Operating Voltage Type and Rating Per Pole in Volts115.0 AC SECOND LOCATION
Mounting Facility Type and Quantity4 THREADED HOLE(S) AND 4 SLOT
Actuator Position DesignationAT EACH POLE
Frequency in Hertz50.0 OR 60.0 ALL LOCATIONS
Unpackaged Unit Weight1.188 POUNDS NOMINAL LBS
Center to Center Distance Between Terminals Parallel to Width1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
External Actuator Linkage ArrangementONE AND TWO LINKED
Distance Between Centerlines of Mounting Facilities Parallel to Body Length2.718 INCHES MINIMUM AND 2.782 INCHES MAXIMUM IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.038 INCHES MINIMUM AND 2.102 INCHES MAXIMUM IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity2
Mounting Surface to Terminal End Distance3.172 INCHES MINIMUM AND 3.296 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole85.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicINSTANTANEOUS SECOND LOCATION
Trip Release CharacteristicTIME DELAY FIRST LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC ALL LOCATIONS
Nominal Thread Size0.138 INCHES IN
Body Length5.768 INCHES MINIMUM AND 5.832 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current35.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT FIRST LOCATION
Manual Actuator Type and Quantity2 TOGGLE
Distance Between Centerlines of Mounting Facilities Parallel to Body Width1.016 INCHES MINIMUM AND 1.036 INCHES MAXIMUM IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
Part NumberManufacturer
CD2-Z-406-1 Heinemann Electric Canada Incdivision of Eaton Corp (CAN)
Reference documents
ReferenceMeaning
CD2-A3A6-85-240-1-11 C/1 Advisory reference — outside the item-of-supply concept
Eaton Corp Heinemann Products Commercial Controls Div
CD2A3A9UP185A240AC12 C/1 Advisory reference — outside the item-of-supply concept
Eaton Corp Heinemann Products Commercial Controls Div
WT-C0078-001 C/1 Advisory reference — outside the item-of-supply concept
Raytheon E-Systems, Inc
CD2A3A6U-P1-85A240AC1-P2-115AC-P 5/9 Secondary reference
Eaton Corp Heinemann Products Commercial Controls Div
CD2-Z-406-1 3/9 Design control — primary reference
Eaton Corp Heinemann Products Commercial Controls Div
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-229-8654?

NSN 5925-01-229-8654 is a Circuit Breaker, manufactured by Heinemann Electric Canada Incdivision of Eaton Corp, classified under FSC 5925, Circuit Breakers. Status: active.

What part numbers are listed for NSN 5925-01-229-8654?

NSN 5925-01-229-8654 has 1 manufacturer part number on file: CD2-Z-406-1 (Heinemann Electric Canada Incdivision of Eaton Corp).

What are the specifications of CD2-Z-406-1?

Key specifications for CD2-Z-406-1: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP FIRST LOCATION; Internal Trip Release Configuration: RELAY TRIP SECOND LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC FIRST LOCATION. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-229-8654 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com