The Circuit Breaker, cataloged under National Stock Number 5925-01-216-1976, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is Circor Instrumentation Technologies, Inc. Dba Hoke Gyrolok. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 2 manufacturer part numbers for this item, enabling identification through both NSN and commercial part number lookups. 4 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-216-1976 |
| Primary Part Number | CD4-Z139-1W |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Manufacturer | Circor Instrumentation Technologies, Inc. Dba Hoke Gyrolok |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 240.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 8 THREADED HOLE(S) AND 4 SLOT |
| Actuator Position Designation | AT EACH POLE |
| Frequency in Hertz | 50.0 OR 60.0 ALL LOCATIONS |
| Unpackaged Unit Weight | 2.700 POUNDS NOMINAL LBS |
| Center to Center Distance Between Terminals Parallel to Width | 1.529 INCHES MINIMUM AND 1.549 INCHES MAXIMUM IN |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 ALL LOCATIONS |
| External Actuator Linkage Arrangement | ONE, TWO, THREE, AND FOUR LINKED |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.740 INCHES MINIMUM AND 2.760 INCHES MAXIMUM IN |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 4.094 INCHES MINIMUM AND 4.114 INCHES MAXIMUM IN |
| Body Height | 3.475 INCHES MINIMUM AND 3.495 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 4 |
| Maximum Continuous Load Current Rating Per Pole | 100.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 5000.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 4.740 INCHES MINIMUM AND 4.760 INCHES MAXIMUM IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 4 TOGGLE |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 1.529 INCHES MINIMUM AND 1.549 INCHES MAXIMUM IN |
| Inclosure Protection Type for Which Designed | MOISTURE RESISTANT AND SHOCK RESISTANT AND VIBRATION RESISTANT |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Part Number | Manufacturer |
|---|---|
| CD4-Z139-1W PRIMARY | Circor Instrumentation Technologies, Inc. Dba Hoke Gyrolok (USA) |
| CD4-Z139-1W | Babcock Communications Ltd (GBR) |
| Reference | Meaning |
|---|---|
| CD4-Z139-1W | 5/9 Secondary reference Heinemann Electric Canada Ltd Divof Eaton Corp |
| CD4-Z139-1W | 5/9 Secondary reference Hoke Inc Dba Hoke Controls Houston Division |
| CD4-Z139-1 | 5/9 Secondary reference Eaton Corp Heinemann Products Commercial Controls Div |
| 602153-01 | 3/9 Design control — primary reference Edo |
NSN 5925-01-216-1976 is a Circuit Breaker, manufactured by Circor Instrumentation Technologies, Inc. Dba Hoke Gyrolok, classified under FSC 5925, Circuit Breakers. Status: active.
NSN 5925-01-216-1976 has 2 manufacturer part numbers on file: CD4-Z139-1W (Circor Instrumentation Technologies, Inc. Dba Hoke Gyrolok), CD4-Z139-1W (Babcock Communications Ltd).
Key specifications for CD4-Z139-1W: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 8 THREADED HOLE(S) AND 4 SLOT. 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.