PartsTable TECHNICAL DATA SHEET
JULY 2026Technical Data Sheet

04-1311Circuit Breaker

Bacharach, Inc. · NSN 5925-01-206-1117 · FSC 5925 · No Item Name Available
Verified by PartsTable
NSN 5925-01-206-1117 — this item is cataloged by the U.S. Government under National Stock Number 5925-01-206-1117. Primary manufacturer part number: 04-1311.
Features
  • Circuit Breaker — FSC 5925
  • Terminal Type and Quantity: 2 CLIP AND 2 COMPRESSION
  • Circuit Protection Type: OVERCURRENT ALL LOCATIONS
  • Actuator Position Designation: AT EACH POLE
  • Trip Release Method: THERMAL-MAGNETIC ALL LOCATIONS
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 125.0 ALL LOCATIONS
  • Trip Delay Time in Seconds Per Rated Continuous Current: 13.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS
  • Reset Method: MANUAL
Applications
  • Applications requiring Plastic Case construction
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-206-1117, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Bacharach, Inc.. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 3 commercial cross-references from 3 manufacturers, enabling identification through both NSN and commercial part number lookups. 2 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-206-1117
Primary Part Number04-1311
Item NameCircuit Breaker
FSC / FSG5925 / 59 — No Item Name Available
ManufacturerBacharach, Inc.
StatusACTIVE
Terminal Type and Quantity2 CLIP AND 2 COMPRESSION
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Actuator Position DesignationAT EACH POLE
Trip Release MethodTHERMAL-MAGNETIC ALL LOCATIONS
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Trip Delay Time in Seconds Per Rated Continuous Current13.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Reset MethodMANUAL
Frequency in Hertz60.0 ALL LOCATIONS
MaterialPLASTIC CASE
Manual Actuator Type and Quantity2 TOGGLE
Main Contact Tripping Mechanism TypeTRIP FREE
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
Trip Release Ambient Temp Rating40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Pole Quantity2
Arc Quenching MethodMAGNETIC BLOWOUT
Storage TypeGENERAL PURPOSE WAREHOUSE
Mounting Facility Type and Quantity4 TERMINAL
Boss Height0.156 INCHES NOMINAL IN
Center to Center Distance Between Terminals Parallel to Width1.000 INCHES NOMINAL IN
Special Handling FeatureMAGNETIC
Fragility FactorMODERATELY RUGGED
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps75000.0 AC ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts120.0 AC AND 240.0 AC ALL LOCATIONS
Body Length3.750 INCHES NOMINAL IN
Body Width2.000 INCHES NOMINAL IN
Body Height2.344 INCHES NOMINAL IN
Inclosure Protection Type for Which DesignedGENERAL PURPOSE
External Actuator Linkage ArrangementONE AND TWO LINKED
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Maximum Continuous Load Current Rating Per Pole20.0 AMPERES AC ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
HAZMATNo
Verified Substitutes 2
5925-00-724-5533 INTERCHANGEABLE
Circuit Breaker
6545-01-523-9363A337 INTERCHANGEABLE
X-Ray Dry Processing,computed Ra
Defense Medical Standardization Board
Cross-Reference Index
Part NumberManufacturer
THQC2120WL General Electric Co Outdoor Breaker Business Section (USA)
04-1311 PRIMARY Bacharach, Inc. (USA)
QC2020W/1265C83G01 Eaton Corporation Dba Eaton Inoac (USA)
Related Parts
5925-00-724-5533INTERCHANGEABLE
CIRCUIT BREAKER
6545-01-523-9363INTERCHANGEABLE
X-RAY DRY PROCESSING,COMPUTED RA
A337

Frequently Asked Questions

What is NSN 5925-01-206-1117?

NSN 5925-01-206-1117 is a Circuit Breaker, manufactured by Bacharach, Inc., classified under FSC 5925 (No Item Name Available). Status: active.

What are the part numbers for NSN 5925-01-206-1117?

NSN 5925-01-206-1117 has 3 cross-referenced part numbers: THQC2120WL (General Electric Co Outdoor Breaker Business Section), 04-1311 (Bacharach, Inc.), QC2020W/1265C83G01 (Eaton Corporation Dba Eaton Inoac).

What NSN replaces 5925-01-206-1117?

There are 2 known substitutes for 5925-01-206-1117: 5925-00-724-5533, 6545-01-523-9363. Verify interchangeability with system specifications before substitution.

What are the specifications of 04-1311?

Key specifications for 04-1311: Terminal Type and Quantity: 2 CLIP AND 2 COMPRESSION; Circuit Protection Type: OVERCURRENT ALL LOCATIONS; Actuator Position Designation: AT EACH POLE; Trip Release Method: THERMAL-MAGNETIC ALL LOCATIONS. 30 total characteristics are documented in the Federal Logistics Information System.

Validated with multiple authoritative sources, including Government, OEM, and Certified sources.
PartsTable Design LLC · partstable.com