The Circuit Breaker, cataloged under National Stock Number 5925-01-187-7404, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 12 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-187-7404 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Fragility Factor | MODERATELY RUGGED |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 1 |
| Maximum Continuous Load Current Rating Per Pole | 7.0 AMPERES AC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Inclosure Protection Type for Which Designed | GENERAL PURPOSE |
| Material | PLASTIC CASE |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Trip Release Method | MAGNETIC SINGLE LOCATION |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| 08-1-000036 | 3/9 Design control — primary reference Nicolet Computer Graphics Div |
| JA1A3A7-2 | C/1 Advisory reference — outside the item-of-supply concept Eaton Corp Heinemann Products Commercial Controls Div |
NSN 5925-01-187-7404 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-187-7404: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Fragility Factor: MODERATELY RUGGED; Circuit Protection Type: OVERCURRENT SINGLE LOCATION. 12 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.