NSN 5925-01-183-3109 · NIIN 011833109 · Part number 5254-583
Raytheon Company Div Rmd Strategic · FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components · CAGE 05869
Government record, cited
NSN 5925-01-183-3109 — this item is cataloged by the U.S. Government under National Stock Number 5925-01-183-3109. Manufacturer of record part number: 5254-583.
Also searched as  5925-01-183-3109 · 5925011833109 · NIIN 011833109 · 01-183-3109 · FSC 5925 Circuit Breakers · CAGE 05869 · 5254-583 · TED134020
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 480.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 4 UNTHREADED HOLE(S)
  • Actuator Position Designation: AT POLE TWO
  • Frequency in Hertz: 60.0 ALL LOCATIONS
  • Center to Center Distance Between Terminals Parallel to Width: 1.375 INCHES NOMINAL IN
  • Fragility Factor: MODERATELY RUGGED
Identification
  • NSN: 5925-01-183-3109
  • NIIN: 011833109
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
  • Primary part number: 5254-583
  • Manufacturer: Raytheon Company Div Rmd Strategic
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-183-3109, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is Raytheon Company Div Rmd Strategic. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 2 manufacturer part numbers for this item, enabling identification through both NSN and commercial part number lookups. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-183-3109
Primary Part Number5254-583
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
ManufacturerRaytheon Company Div Rmd Strategic
StatusACTIVE
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts480.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity4 UNTHREADED HOLE(S)
Actuator Position DesignationAT POLE TWO
Frequency in Hertz60.0 ALL LOCATIONS
Center to Center Distance Between Terminals Parallel to Width1.375 INCHES NOMINAL IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Length4.880 INCHES NOMINAL IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width4.125 INCHES NOMINAL IN
Body Height3.380 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Unthreaded Mounting Hole Diameter0.188 INCHES NOMINAL IN
Pole Quantity3
Maximum Continuous Load Current Rating Per Pole20.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps15000.0 AC ALL LOCATIONS
Body Length6.310 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current45.000 MINIMUM AT 200 PCT AND 150.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Distance Between Centerlines of Mounting Facilities Parallel to Body Width1.375 INCHES NOMINAL IN
Inclosure Protection Type for Which DesignedGENERAL PURPOSE
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Trip Release Ambient Temp Rating50.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Terminal Type and Quantity6 COMPRESSION
Main Contact Tripping Mechanism TypeTRIP FREE
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
Part NumberManufacturer
TED134020 General Electric Company Dba Ge (USA)
5254-583 PRIMARY Raytheon Company Div Rmd Strategic (USA)

Frequently Asked Questions

What is NSN 5925-01-183-3109?

NSN 5925-01-183-3109 is a Circuit Breaker, manufactured by Raytheon Company Div Rmd Strategic, classified under FSC 5925, Circuit Breakers. Status: active.

What part numbers are listed for NSN 5925-01-183-3109?

NSN 5925-01-183-3109 has 2 manufacturer part numbers on file: TED134020 (General Electric Company Dba Ge), 5254-583 (Raytheon Company Div Rmd Strategic).

What are the specifications of 5254-583?

Key specifications for 5254-583: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 480.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 UNTHREADED HOLE(S); Actuator Position Designation: AT POLE TWO. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-183-3109 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.