PartsTable TECHNICAL DATA SHEET
NSN 5925-01-166-7560Government record, cited

Circuit Breaker5925-01-166-7560

NSN 5925-01-166-7560 · NIIN 011667560
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-166-7560 · 5925011667560 · NIIN 011667560 · 01-166-7560 · FSC 5925 Circuit Breakers
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 6 CLIP
  • Actuator Position Designation: AT POLE TWO
  • Ultimate Trip Time Per Pole in Seconds: 0.200 MINIMUM AND 7.000 MAXIMUM ALL LOCATIONS
  • Frequency in Hertz: 50.0 OR 60.0 ALL LOCATIONS
Identification
  • NSN: 5925-01-166-7560
  • NIIN: 011667560
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-166-7560, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 26 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-166-7560
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts250.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity6 CLIP
Actuator Position DesignationAT POLE TWO
Ultimate Trip Time Per Pole in Seconds0.200 MINIMUM AND 7.000 MAXIMUM ALL LOCATIONS
Frequency in Hertz50.0 OR 60.0 ALL LOCATIONS
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
External Actuator Linkage ArrangementONE, TWO, AND THREE LINKED
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.170 INCHES NOMINAL IN
Body Height1.770 INCHES MAXIMUM IN
Pole Quantity3
Maximum Continuous Load Current Rating Per Pole20.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps1000.0 AC ALL LOCATIONS
Body Length2.000 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current0.050 MINIMUM AT 200 PCT AND 1.000 MAXIMUM AT 200 PCT AND 0.020 MINIMUM AT 400 PCT AND 0.230 MAXIMUM AT 400 PCT AND 0.005 MINIMUM AT 800 PCT AND 0.090 MAXIMUM AT 800 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity6 TAB, SOLDER LUG
Main Contact Tripping Mechanism TypeTRIP FREE
Boss Height0.125 INCHES NOMINAL IN
Trip Release MethodMAGNETIC-HYDRAULIC ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
203-222-1-61-203-4-1-1-A 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-166-7560?

NSN 5925-01-166-7560 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-166-7560?

Key specifications for 5925-01-166-7560: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 6 CLIP. 26 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-166-7560 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com