The Circuit Breaker, cataloged under National Stock Number 5925-01-162-4002, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-162-4002 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 250.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 6 THREADED HOLE(S) |
| Actuator Position Designation | AT EACH POLE |
| Switch Terminal Type | TAB, SOLDER LUG |
| Frequency in Hertz | 400.0 ALL LOCATIONS |
| Unpackaged Unit Weight | 9.500 OUNCES NOMINAL OZ |
| Center to Center Distance Between Terminals Parallel to Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM IN |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| Switch Voltage Rating and Type in Volts | 250.0 AC AND 30.0 DC |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 ALL LOCATIONS |
| External Actuator Linkage Arrangement | ONE, TWO, AND THREE LINKED |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM IN |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Switch Location and Position Designation | INTERNAL AT POLE ONE |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 3 |
| Mounting Surface to Terminal End Distance | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM IN |
| Maximum Continuous Load Current Rating Per Pole | 60.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 2.400 MINIMUM AT 200 PCT AND 22.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 3 TOGGLE |
| Switch Current Rating and Type in Amps | 10.0 AC AND 5.0 DC |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| AM3-C2C3C3-60-2 | 5/9 Secondary reference Eaton Corp Heinemann Products Commercial Controls Div |
| AM3-C2-0060-02E | 5/9 Secondary reference Eaton Corp Heinemann Products Commercial Controls Div |
| 5050214-1 | 3/9 Design control — primary reference Signals Warfare Project Manager |
NSN 5925-01-162-4002 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-162-4002: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 6 THREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.