The Circuit Breaker, cataloged under National Stock Number 5925-01-119-2006, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 1 item shares a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-119-2006 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Operating Voltage Type and Rating Per Pole in Volts | 500.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 8 UNTHREADED HOLE(S) |
| Actuator Position Designation | AT POLE TWO |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Body Style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 150.0 ALL LOCATIONS |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 19.750 INCHES NOMINAL IN |
| Arc Quenching Method | AIR |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 16.000 INCHES NOMINAL IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Unthreaded Mounting Hole Diameter | 0.406 INCHES NOMINAL IN |
| Pole Quantity | 3 |
| Mounting Surface to Terminal End Distance | 12.781 INCHES NOMINAL IN |
| Maximum Continuous Load Current Rating Per Pole | 1600.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 75000.0 AC ALL LOCATIONS |
| Body Length | 22.000 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 20.000 MINIMUM AT 600 PCT AND 32.000 MAXIMUM AT 600 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Nondefinitive Spec/std Data | AQB-A1601 TYPE |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 4.000 INCHES NOMINAL IN |
| Inclosure Protection Type for Which Designed | SHOCK RESISTANT AND VIBRATION RESISTANT |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Trip Release Ambient Temp Rating | 50.0 CELSIUS NOMINAL ALL LOCATIONS DEGC |
| Terminal Type and Quantity | 6 BUS BAR |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Boss Height | 0.875 INCHES NOMINAL IN |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| AQB-A1601 | 2/2 Government specification standardization U.S. Government activity |
| MIL-DTL-17361/14 | 4/1 Identification reference U.S. Government activity |
| MIL-C-17361 | 5/9 Secondary reference U.S. Government activity |
NSN 5925-01-119-2006 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
1 possible match (shared part number, not a government interchangeability claim): 5925-01-642-1519. Verify interchangeability with system specifications before substitution.
Key specifications for 5925-01-119-2006: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 500.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 8 UNTHREADED HOLE(S); Actuator Position Designation: AT POLE TWO. 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.