PartsTable TECHNICAL DATA SHEET
NSN 5925-01-101-9479Government record, cited

Circuit Breaker5925-01-101-9479

NSN 5925-01-101-9479 · NIIN 011019479
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-101-9479 · 5925011019479 · NIIN 011019479 · 01-101-9479 · FSC 5925 Circuit Breakers · JB2-A3-CB-A-15-3 · JB2S-A3-A-15-3
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 4 CLIP
  • Actuator Position Designation: AT EACH POLE
  • Frequency in Hertz: 50.0 OR 60.0 ALL LOCATIONS
  • Unpackaged Unit Weight: 5.000 OUNCES NOMINAL OZ
Identification
  • NSN: 5925-01-101-9479
  • NIIN: 011019479
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-101-9479, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-101-9479
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts250.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity4 CLIP
Actuator Position DesignationAT EACH POLE
Frequency in Hertz50.0 OR 60.0 ALL LOCATIONS
Unpackaged Unit Weight5.000 OUNCES NOMINAL OZ
Center to Center Distance Between Terminals Parallel to Width0.923 INCHES MINIMUM AND 0.987 INCHES MAXIMUM IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
External Actuator Linkage ArrangementONE AND TWO LINKED
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width1.718 INCHES MINIMUM AND 1.782 INCHES MAXIMUM IN
Body Height1.811 INCHES MINIMUM AND 1.875 INCHES MAXIMUM IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity2
Maximum Continuous Load Current Rating Per Pole15.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC ALL LOCATIONS
Body Length2.418 INCHES MINIMUM AND 2.482 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current0.150 MINIMUM AT 200 PCT AND 1.500 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity2 TOGGLE
Inclosure Protection Type for Which DesignedFUNGUS RESISTANT AND MOISTURE RESISTANT
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity4 QUICK DISCONNECT, MALE
Main Contact Tripping Mechanism TypeTRIP FREE
Boss Height0.093 INCHES MINIMUM AND 0.157 INCHES MAXIMUM IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
JB2-A3-CB-A-15-3 5/9 Secondary reference
Eaton Corp Heinemann Products Commercial Controls Div
JB2S-A3-A-15-3 3/9 Design control — primary reference
Eaton Corp Heinemann Products Commercial Controls Div
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-01-101-9479?

NSN 5925-01-101-9479 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-101-9479?

Key specifications for 5925-01-101-9479: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 CLIP. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-101-9479 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.