The Circuit Breaker, cataloged under National Stock Number 5925-01-064-7828, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-064-7828 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Operating Voltage Type and Rating Per Pole in Volts | 250.0 AC SINGLE LOCATION |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S) |
| Actuator Position Designation | AT POLE ONE |
| Frequency in Hertz | 60.0 SINGLE LOCATION |
| Unpackaged Unit Weight | 4.250 OUNCES NOMINAL OZ |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | SINGLE POLE TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 SINGLE LOCATION |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM IN |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Body Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 1 |
| Mounting Surface to Terminal End Distance | 2.611 INCHES NOMINAL IN |
| Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES AC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC SINGLE LOCATION |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.150 MINIMUM AT 200 PCT AND 1.500 MAXIMUM AT 200 PCT AND 0.055 MINIMUM AT 300 PCT AND 0.450 MAXIMUM AT 300 PCT AND 0.030 MINIMUM AT 400 PCT AND 0.230 MAXIMUM AT 400 PCT AND 0.003 MINIMUM AT 1000 PCT AND 0.003 MAXIMUM AT 1000 PCT SINGLE LOCATION |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Inclosure Protection Type for Which Designed | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Terminal Type and Quantity | 2 THREADED STUD |
| Special Handling Feature | MAGNETIC |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| AM1-A3-30-3 | 3/9 Design control — primary reference Eaton Corp Heinemann Products Commercial Controls Div |
NSN 5925-01-064-7828 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-064-7828: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.