PartsTable TECHNICAL DATA SHEET
NSN 5925-01-056-7608Government record, cited

Circuit Breaker5925-01-056-7608

NSN 5925-01-056-7608 · NIIN 010567608
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-056-7608 · 5925010567608 · NIIN 010567608 · 01-056-7608 · FSC 5925 Circuit Breakers · 20L4-103 · AM3-Z633-1 · AM3-A3A3A16
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP SECOND LOCATION
  • Internal Trip Release Configuration: SERIES TRIP FIRST LOCATION
  • Internal Trip Release Configuration: SERIES/RELAY TRIP THIRD LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 6 THREADED HOLE(S)
  • Actuator Position Designation: AT EACH POLE
Identification
  • NSN: 5925-01-056-7608
  • NIIN: 010567608
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-056-7608, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-056-7608
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP SECOND LOCATION
Internal Trip Release ConfigurationSERIES TRIP FIRST LOCATION
Internal Trip Release ConfigurationSERIES/RELAY TRIP THIRD LOCATION
Operating Voltage Type and Rating Per Pole in Volts250.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity6 THREADED HOLE(S)
Actuator Position DesignationAT EACH POLE
Frequency in Hertz50.0 OR 60.0 ALL LOCATIONS
Unpackaged Unit Weight10.000 OUNCES NOMINAL OZ
Center to Center Distance Between Terminals Parallel to Width0.687 INCHES MINIMUM AND 0.813 INCHES MAXIMUM IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
External Actuator Linkage ArrangementONE, TWO, AND THREE LINKED
Distance Between Centerlines of Mounting Facilities Parallel to Body Length2.000 INCHES MINIMUM AND 2.127 INCHES MAXIMUM IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.187 INCHES MINIMUM AND 2.313 INCHES MAXIMUM IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Trip Release Duty CycleCONTINUOUS THIRD LOCATION
Pole Quantity3
Mounting Surface to Terminal End Distance2.375 INCHES MINIMUM AND 2.501 INCHES MAXIMUM IN
Maximum Continuous Load Current Rating Per Pole40.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY FIRST LOCATION
Trip Release CharacteristicTIME DELAY SECOND LOCATION
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY THIRD LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps1000.0 AC ALL LOCATIONS
Nominal Thread Size0.138 INCHES IN
Body Length2.437 INCHES MINIMUM AND 2.563 INCHES MAXIMUM IN
Trip Delay Time in Seconds Per Rated Continuous Current2.000 MINIMUM AT 200 PCT AND 20.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
20L4-103 3/2 Design control — primary reference
U.S. Government activity
AM3-Z633-1 5/9 Secondary reference
Eaton Corp Heinemann Products Commercial Controls Div
AM3-A3A3A16 5/9 Secondary reference
Eaton Corp Heinemann Products Commercial Controls Div

Frequently Asked Questions

What is NSN 5925-01-056-7608?

NSN 5925-01-056-7608 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-056-7608?

Key specifications for 5925-01-056-7608: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SECOND LOCATION; Internal Trip Release Configuration: SERIES TRIP FIRST LOCATION; Internal Trip Release Configuration: SERIES/RELAY TRIP THIRD LOCATION. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-056-7608 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com