PartsTable TECHNICAL DATA SHEET
NSN 5925-01-032-1122Government record, cited

Circuit Breaker5925-01-032-1122

NSN 5925-01-032-1122 · NIIN 010321122
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-01-032-1122 · 5925010321122 · NIIN 010321122 · 01-032-1122 · FSC 5925 Circuit Breakers · AM17-2.5A120V60C56 · AM-17-2.5A · 120104-008C · 120104-008 · DMS83059
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC SINGLE LOCATION
  • Mounting Facility Type and Quantity: 2 THREADED HOLE(S)
  • Actuator Position Designation: AT POLE ONE
  • Frequency in Hertz: 60.0 SINGLE LOCATION
  • Fragility Factor: MODERATELY RUGGED
Identification
  • NSN: 5925-01-032-1122
  • NIIN: 010321122
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-01-032-1122, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 7 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-01-032-1122
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Internal Trip Release ConfigurationSERIES TRIP SINGLE LOCATION
Operating Voltage Type and Rating Per Pole in Volts120.0 AC SINGLE LOCATION
Mounting Facility Type and Quantity2 THREADED HOLE(S)
Actuator Position DesignationAT POLE ONE
Frequency in Hertz60.0 SINGLE LOCATION
Fragility FactorMODERATELY RUGGED
Body StyleSINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 SINGLE LOCATION
Distance Between Centerlines of Mounting Facilities Parallel to Body Length1.812 INCHES NOMINAL IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT SINGLE LOCATION
Body Width0.750 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity1
Mounting Surface to Terminal End Distance2.000 INCHES NOMINAL IN
Maximum Continuous Load Current Rating Per Pole2.5 AMPERES AC SINGLE LOCATION
Trip Release CharacteristicTIME DELAY SINGLE LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps3500.0 AC SINGLE LOCATION
Nominal Thread Size0.138 INCHES IN
Body Length2.500 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current0.380 MINIMUM AT 200 PCT AND 1.200 MAXIMUM AT 200 PCT SINGLE LOCATION
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedFUNGUS RESISTANT AND EXPLOSION RESISTANT
Thread Quantity Per Inch32
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Terminal Type and Quantity2 SCREW
Special Handling FeatureMAGNETIC
Main Contact Tripping Mechanism TypeTRIP FREE
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
AM17-2.5A120V60C56 5/9 Secondary reference
Eaton Corp Heinemann Products Commercial Controls Div
AM-17-2.5A C/1 Advisory reference — outside the item-of-supply concept
Eaton Corp Heinemann Products Commercial Controls Div
120104-008C C/1 Advisory reference — outside the item-of-supply concept
U.S. Government activity
120104-008 5/9 Secondary reference
U.S. Government activity
DMS83059 5/9 Secondary reference
Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (vendor Item Drawings)
DMS 83059B 5/9 Secondary reference
Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (vendor Item Drawings)
237691-008 3/2 Design control — primary reference
U.S. Government activity

Frequently Asked Questions

What is NSN 5925-01-032-1122?

NSN 5925-01-032-1122 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-01-032-1122?

Key specifications for 5925-01-032-1122: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-01-032-1122 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com