The Circuit Breaker, cataloged under National Stock Number 5925-01-023-4606, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 25 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-01-023-4606 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Operating Voltage Type and Rating Per Pole in Volts | 480.0 AC AND 250.0 DC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 4 UNTHREADED HOLE(S) |
| Actuator Position Designation | AT POLE TWO |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | RECTANGULAR DIMENSIONAL ENVELOPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 130.0 SINGLE LOCATION |
| Arc Quenching Method | AIR |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Unthreaded Mounting Hole Diameter | 0.453 INCHES NOMINAL IN |
| Pole Quantity | 3 |
| Maximum Continuous Load Current Rating Per Pole | 40.0 AMPERES AC AND 40.0 AMPERES DC ALL LOCATIONS |
| Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 14000.0 AC AND 10000.0 DC ALL LOCATIONS |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Inclosure Protection Type for Which Designed | SHOCK RESISTANT AND VIBRATION RESISTANT |
| Cubic Measure | 58.250 CUBIC INCHES |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Trip Release Ambient Temp Rating | 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC |
| Terminal Type and Quantity | 6 COMPRESSION |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| NEF433040 | 5/9 Secondary reference Challenger Electrical Equipment Corp |
| NEF437040 | 3/9 Design control — primary reference American Circuit Breaker Corp |
NSN 5925-01-023-4606 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-01-023-4606: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 480.0 AC AND 250.0 DC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 UNTHREADED HOLE(S); Overall Height: 3.219 INCHES NOMINAL IN. 25 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.