The Circuit Breaker, cataloged under National Stock Number 5925-00-906-7811, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Federal Specifications Promulgated by General Services Administration Washington DC. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 7 commercial cross-references from 4 manufacturers, enabling identification through both NSN and commercial part number lookups. 4 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-906-7811 |
| Primary Part Number | W-C-375/6 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — No Item Name Available |
| Manufacturer | Federal Specifications Promulgated by General Services Administration Washington DC |
| Status | ACTIVE |
| Actuator Function | TRIP-RESET |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 135.0 ALL LOCATIONS |
| Trip Release Ambient Temp Rating | 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Terminal Type and Quantity | 4 CLIP |
| Test Data Document | 81348-W-C-375 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| Actuator Position Designation | AT EACH POLE |
| Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC ALL LOCATIONS |
| Material | PLASTIC CASE |
| Manual Actuator Type and Quantity | 2 TOGGLE |
| Inclosure Protection Type for Which Designed | CORROSION RESISTANT |
| External Actuator Linkage Arrangement | ONE AND TWO LINKED |
| Reset Method | MANUAL |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Specification/standard Data | 81349-W-C-375/6 GOVERNMENT SPECIFICATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 2.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 10000.0 AC ALL LOCATIONS |
| Trip Release Method | THERMAL-MAGNETIC ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 240.0 AC ALL LOCATIONS |
| Center to Center Distance Between Terminals Parallel to Width | 0.552 INCHES MINIMUM AND 0.578 INCHES MAXIMUM IN |
| Fragility Factor | MODERATELY RUGGED |
| Pole Quantity | 2 |
| Special Handling Feature | MAGNETIC |
| Boss Height | 0.188 INCHES NOMINAL IN |
| Mounting Facility Type and Quantity | 2 TERMINAL |
| Body Length | 2.987 INCHES MINIMUM AND 3.013 INCHES MAXIMUM IN |
| Body Width | 1.464 INCHES MINIMUM AND 1.496 INCHES MAXIMUM IN |
| Body Height | 2.466 INCHES MINIMUM AND 2.594 INCHES MAXIMUM IN |
| Acquisition Status | ACTIVE |
| HAZMAT | No |
| Part Number | Manufacturer |
|---|---|
| W-C-375/6 | Federal Specifications Promulgated by General Services Administration Washington DC (USA) |
| WC375/06-002 | Federal Specifications Promulgated by General Services Administration Washington DC (USA) |
| WC375/06-002 | Military Specifications Promulgated by Military Departments/agencies Under Authority of Defense Standardization Manual 4120 3-M |
| CH220 | Eaton Corp Opns & Technical Center (USA) |
| EC2020SFC | Drs Naval Power Systems Inc Dba Drs Power & Control Technologies Inc (USA) |
| W-C-375/6 | Military Specifications Promulgated by Military Departments/agencies Under Authority of Defense Standardization Manual 4120 3-M |
| CH220 | Drs Naval Power Systems Inc Dba Drs Power & Control Technologies Inc (USA) |
NSN 5925-00-906-7811 is a Circuit Breaker, manufactured by Federal Specifications Promulgated by General Services Administration Washington DC, classified under FSC 5925 (No Item Name Available). Status: active.
NSN 5925-00-906-7811 has 7 cross-referenced part numbers: W-C-375/6 (Federal Specifications Promulgated by General Services Administration Washington DC), WC375/06-002 (Federal Specifications Promulgated by General Services Administration Washington DC), WC375/06-002 (Military Specifications Promulgated by Military Departments/agencies Under Authority of Defense Standardization Manual 4120 3-M), CH220 (Eaton Corp Opns & Technical Center), EC2020SFC (Drs Naval Power Systems Inc Dba Drs Power & Control Technologies Inc) and 2 more.
There are 4 known substitutes for 5925-00-906-7811: 5925-00-233-9255, 4520-00-902-7132, 5925-00-914-3636 and 1 more. Verify interchangeability with system specifications before substitution.
Key specifications for W-C-375/6: Actuator Function: TRIP-RESET; Circuit Protection Type: OVERCURRENT ALL LOCATIONS; Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 135.0 ALL LOCATIONS; Trip Release Ambient Temp Rating: 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC. 30 total characteristics are documented in the Federal Logistics Information System.