PartsTable TECHNICAL DATA SHEET
JULY 2026Technical Data Sheet

423100Circuit Breaker

Challenger Electrical Equipment Corp · NSN 5925-00-901-1652 · FSC 5925 · No Item Name Available
Verified by PartsTable
NSN 5925-00-901-1652 — this item is cataloged by the U.S. Government under National Stock Number 5925-00-901-1652. Primary manufacturer part number: 423100.
Features
  • Circuit Breaker — FSC 5925
  • Actuator Position Designation: AT POLE TWO
  • Maximum Continuous Load Current Rating Per Pole: 100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS
  • Trip Release Ambient Temp Rating: 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
  • Trip Delay Time in Seconds Per Rated Continuous Current: 24.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS
  • Operating Voltage Type and Rating Per Pole in Volts: 480.0 AC AND 250.0 DC ALL LOCATIONS
  • Trip Release Method: THERMAL-MAGNETIC ALL LOCATIONS
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 125.0 ALL LOCATIONS
Applications
  • Applications requiring Plastic Case construction
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-901-1652, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Challenger Electrical Equipment Corp. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 2 commercial cross-references from 1 manufacturer, enabling identification through both NSN and commercial part number lookups. 2 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-901-1652
Primary Part Number423100
Item NameCircuit Breaker
FSC / FSG5925 / 59 — No Item Name Available
ManufacturerChallenger Electrical Equipment Corp
StatusACTIVE
Actuator Position DesignationAT POLE TWO
Maximum Continuous Load Current Rating Per Pole100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS
Trip Release Ambient Temp Rating40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Trip Delay Time in Seconds Per Rated Continuous Current24.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Operating Voltage Type and Rating Per Pole in Volts480.0 AC AND 250.0 DC ALL LOCATIONS
Trip Release MethodTHERMAL-MAGNETIC ALL LOCATIONS
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Actuator FunctionTRIP-RESET
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
MaterialPLASTIC CASE
Inclosure Protection Type for Which DesignedFUNGUS RESISTANT
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps15000.0 AC AND 10000.0 DC ALL LOCATIONS
Mounting Slot Width0.250 INCHES NOMINAL IN
Manual Actuator Type and Quantity1 TOGGLE
Reset MethodMANUAL
Terminal Type and Quantity4 COMPRESSION
Frequency in Hertz60.0 ALL LOCATIONS
Main Contact Tripping Mechanism TypeTRIP FREE
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Width2.700 INCHES NOMINAL IN
Center to Center Distance Between Terminals Parallel to Length5.219 INCHES NOMINAL IN
Center to Center Distance Between Terminals Parallel to Width1.500 INCHES NOMINAL IN
Pole Quantity2
Mounting Facility Type and Quantity4 SLOT
Arc Quenching MethodMAGNETIC BLOWOUT
Body Height3.406 INCHES NOMINAL IN
Body Width2.750 INCHES NOMINAL IN
Body Length6.062 INCHES NOMINAL IN
Body StyleMULTIPOLE-SINGLE ACTUATOR TYPE
Boss Height0.250 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
HAZMATNo
Verified Substitutes 2
5930-00-919-4460423-100 INTERCHANGEABLE
Switch,rotary
Safran Electronics & Defense, Avionics Usa, Llc Dba Use CAGE Code 879b2 for Cataloging
6210-01-074-1577423100 INTERCHANGEABLE
Lens,light
Air Systems Components Inc Dba Air System Components Inc Div Trion Iaq Div
Cross-Reference Index
Part NumberManufacturer
423100 Challenger Electrical Equipment Corp (USA)
NEF421100 Challenger Electrical Equipment Corp (USA)
Related Parts
5930-00-919-4460INTERCHANGEABLE
SWITCH,ROTARY
423-100
6210-01-074-1577INTERCHANGEABLE
LENS,LIGHT
423100

Frequently Asked Questions

What is NSN 5925-00-901-1652?

NSN 5925-00-901-1652 is a Circuit Breaker, manufactured by Challenger Electrical Equipment Corp, classified under FSC 5925 (No Item Name Available). Status: active.

What are the part numbers for NSN 5925-00-901-1652?

NSN 5925-00-901-1652 has 2 cross-referenced part numbers: 423100 (Challenger Electrical Equipment Corp), NEF421100 (Challenger Electrical Equipment Corp).

What NSN replaces 5925-00-901-1652?

There are 2 known substitutes for 5925-00-901-1652: 5930-00-919-4460, 6210-01-074-1577. Verify interchangeability with system specifications before substitution.

What are the specifications of 423100?

Key specifications for 423100: Actuator Position Designation: AT POLE TWO; Maximum Continuous Load Current Rating Per Pole: 100.0 AMPERES AC AND 100.0 AMPERES DC ALL LOCATIONS; Trip Release Ambient Temp Rating: 40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC; Trip Delay Time in Seconds Per Rated Continuous Current: 24.000 MINIMUM AT 200 PCT AND 65.000 MAXIMUM AT 200 PCT ALL LOCATIONS. 30 total characteristics are documented in the Federal Logistics Information System.

Validated with multiple authoritative sources, including Government, OEM, and Certified sources.
PartsTable Design LLC · partstable.com