The Circuit Breaker, cataloged under National Stock Number 5925-00-826-6901, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Eaton Corp Heinemann Products Commercial Controls Div. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 3 commercial cross-references from 2 manufacturers, enabling identification through both NSN and commercial part number lookups. 5 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-826-6901 |
| Primary Part Number | 62-467AMG4-15-250VAC-1-60H2-1REL |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — No Item Name Available |
| Manufacturer | Eaton Corp Heinemann Products Commercial Controls Div |
| Status | ACTIVE |
| Inclosure Protection Type for Which Designed | FUNGUS RESISTANT AND MOISTURE RESISTANT |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.302 INCHES MINIMUM AND 2.322 INCHES MAXIMUM IN |
| Maximum Continuous Load Current Rating Per Pole | 15.0 AMPERES AC ALL LOCATIONS |
| Internal Trip Release Configuration | RELAY TRIP FIRST LOCATION |
| Material | PLASTIC CASE |
| Center to Center Distance Between Terminals Parallel to Length | 4.349 INCHES MINIMUM AND 4.369 INCHES MAXIMUM IN |
| Mounting Facility Type and Quantity | 4 THREADED HOLE(S) |
| Terminal Type and Quantity | 6 THREADED STUD AND 2 WIRE LEAD |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Nominal Thread Size | 0.190 INCHES IN |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 5000.0 AC ALL LOCATIONS |
| Actuator Position Designation | AT POLE TWO |
| Internal Trip Release Configuration | SERIES TRIP THIRD LOCATION |
| Thread Series Designator | UNF |
| Trip Delay Time in Seconds Per Rated Continuous Current | 70000.000 NOMINAL AT 200 PCT AND 20000.000 NOMINAL AT 300 PCT ALL LOCATIONS |
| Fragility Factor | MODERATELY RUGGED |
| Operating Voltage Type and Rating Per Pole in Volts | 250.0 AC ALL LOCATIONS |
| Trip Release Method | MAGNETIC ALL LOCATIONS |
| Internal Trip Release Configuration | SERIES TRIP SECOND LOCATION |
| Center to Center Distance Between Terminals Parallel to Width | 0.974 INCHES MINIMUM AND 0.994 INCHES MAXIMUM IN |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Reset Method | MANUAL |
| Actuator Function | TRIP-RESET |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 ALL LOCATIONS |
| Ultimate Trip Time Per Pole in Seconds | 10000.000 NOMINAL ALL LOCATIONS |
| Boss Height | 0.209 INCHES MINIMUM AND 0.229 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Acquisition Status | ACTIVE |
| HAZMAT | No |
| Part Number | Manufacturer |
|---|---|
| 62-467AMG4-15-250VAC-1-60H2-1REL | Eaton Corp Heinemann Products Commercial Controls Div (USA) |
| 26072 | Bangor Mfg Co Div of Applied Power Inc (USA) |
| 62-467M6 | Eaton Corp Heinemann Products Commercial Controls Div (USA) |
NSN 5925-00-826-6901 is a Circuit Breaker, manufactured by Eaton Corp Heinemann Products Commercial Controls Div, classified under FSC 5925 (No Item Name Available). Status: active.
NSN 5925-00-826-6901 has 3 cross-referenced part numbers: 62-467AMG4-15-250VAC-1-60H2-1REL (Eaton Corp Heinemann Products Commercial Controls Div), 26072 (Bangor Mfg Co Div of Applied Power Inc), 62-467M6 (Eaton Corp Heinemann Products Commercial Controls Div).
There are 5 known substitutes for 5925-00-826-6901: 5950-00-156-0649, 6105-00-196-4957, 5950-00-905-9056 and 2 more. Verify interchangeability with system specifications before substitution.
Key specifications for 62-467AMG4-15-250VAC-1-60H2-1REL: Inclosure Protection Type for Which Designed: FUNGUS RESISTANT AND MOISTURE RESISTANT; Frequency in Hertz: 60.0 ALL LOCATIONS; Distance Between Centerlines of Mounting Facilities Parallel to Body Length: 2.302 INCHES MINIMUM AND 2.322 INCHES MAXIMUM IN; Maximum Continuous Load Current Rating Per Pole: 15.0 AMPERES AC ALL LOCATIONS. 30 total characteristics are documented in the Federal Logistics Information System.