The Circuit Breaker, cataloged under National Stock Number 5925-00-825-5486, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is Westinghouse Electric Corp. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 2 manufacturer part numbers for this item, enabling identification through both NSN and commercial part number lookups. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-825-5486 |
| Primary Part Number | 314C495G15 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Manufacturer | Westinghouse Electric Corp |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Operating Voltage Type and Rating Per Pole in Volts | 125.0 AC SINGLE LOCATION |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S) |
| Actuator Position Designation | AT POLE ONE |
| Ultimate Trip Time Per Pole in Seconds | 1.000 MINIMUM AND 6.000 MAXIMUM SINGLE LOCATION |
| Switch Terminal Type | TAB, SOLDER LUG |
| Frequency in Hertz | 60.0 SINGLE LOCATION |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | SINGLE POLE TYPE |
| Switch Voltage Rating and Type in Volts | 250.0 AC AND 50.0 DC |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 SINGLE LOCATION |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.052 INCHES MINIMUM AND 2.072 INCHES MAXIMUM IN |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Switch Location and Position Designation | INTERNAL AT POLE ONE |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Body Width | 0.130 INCHES MINIMUM AND 0.150 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 1 |
| Mounting Surface to Terminal End Distance | 2.461 INCHES MINIMUM AND 2.481 INCHES MAXIMUM IN |
| Maximum Continuous Load Current Rating Per Pole | 2.0 AMPERES AC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 2000.0 AC SINGLE LOCATION |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.250 MINIMUM AT 200 PCT AND 0.850 MAXIMUM AT 200 PCT AND 0.090 MINIMUM AT 300 PCT AND 0.280 MAXIMUM AT 300 PCT SINGLE LOCATION |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Switch Current Rating and Type in Amps | 2.5 AC AND 1.0 DC |
| Inclosure Protection Type for Which Designed | FUNGUS RESISTANT AND MOISTURE RESISTANT AND EXPLOSION RESISTANT |
| Switch Contact Arrangement | SINGLE POLE, DOUBLE THROW |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Part Number | Manufacturer |
|---|---|
| 314C495G15 | Westinghouse Electric Corp (USA) |
| W91D11-3-2 | Te Connectivity Corporation (USA) |
| Reference | Meaning |
|---|---|
| 126-202-101 | 5/9 Secondary reference Wood Electric Operations Potter and Brumfield Div Amf Inc |
| 314C495G15 | 5/2 Secondary reference U.S. Government activity |
| AM12HKMG6-2-7 | 3/9 Design control — primary reference Eaton Corp Heinemann Products Commercial Controls Div |
NSN 5925-00-825-5486 is a Circuit Breaker, manufactured by Westinghouse Electric Corp, classified under FSC 5925, Circuit Breakers. Status: active.
NSN 5925-00-825-5486 has 2 manufacturer part numbers on file: 314C495G15 (Westinghouse Electric Corp), W91D11-3-2 (Te Connectivity Corporation).
Key specifications for 314C495G15: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 125.0 AC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.