PartsTable TECHNICAL DATA SHEET
NSN 5925-00-810-4898Government record, cited

Circuit Breaker5925-00-810-4898

NSN 5925-00-810-4898 · NIIN 008104898
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-00-810-4898 · 5925008104898 · NIIN 008104898 · 00-810-4898 · FSC 5925 Circuit Breakers · TE122040 · TE122040
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 250.0 DC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 2 THREADED HOLE(S)
  • Body Style: SINGLE POLE TYPE
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 150.0 ALL LOCATIONS
  • Arc Quenching Method: AIR
  • Circuit Protection Type: OVERCURRENT ALL LOCATIONS
Identification
  • NSN: 5925-00-810-4898
  • NIIN: 008104898
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-810-4898, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 20 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-810-4898
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts240.0 AC AND 250.0 DC ALL LOCATIONS
Mounting Facility Type and Quantity2 THREADED HOLE(S)
Body StyleSINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent150.0 ALL LOCATIONS
Arc Quenching MethodAIR
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.750 INCHES NOMINAL IN
Body Height3.380 INCHES NOMINAL IN
Trip Release Duty CycleCONTINUOUS ALL LOCATIONS
Pole Quantity2
Maximum Continuous Load Current Rating Per Pole40.0 AMPERES AC AND 40.0 AMPERES DC ALL LOCATIONS
Trip Release CharacteristicINSTANTANEOUS AND TIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps7500.0 AC AND 7500.0 DC ALL LOCATIONS
Body Length6.310 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current92.000 MINIMUM AT 150 PCT AND 400.000 MAXIMUM AT 150 PCT AND 30.000 MINIMUM AT 200 PCT AND 90.000 MAXIMUM AT 200 PCT ALL LOCATIONS
MaterialPLASTIC CASE
Trip Release Ambient Temp Rating25.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Terminal Type and Quantity4 SCREW
Trip Release MethodTHERMAL ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
TE122040 3/9 Design control — primary reference
General Electric Co General Purpose Control Dept
TE122040 5/9 Secondary reference
General Electric Company
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-00-810-4898?

NSN 5925-00-810-4898 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-00-810-4898?

Key specifications for 5925-00-810-4898: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 250.0 DC ALL LOCATIONS; Mounting Facility Type and Quantity: 2 THREADED HOLE(S); Body Style: SINGLE POLE TYPE. 20 specifications are documented in the U.S. Government catalog.

Is NSN 5925-00-810-4898 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com