The Circuit Breaker, cataloged under National Stock Number 5925-00-810-2107, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-810-2107 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 208.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 4 THREADED HOLE(S) AND 4 UNTHREADED HOLE(S) |
| Actuator Position Designation | AT POLE TWO |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Unpackaged Unit Weight | 48.000 OUNCES NOMINAL OZ |
| Center to Center Distance Between Terminals Parallel to Width | 1.240 INCHES MINIMUM AND 1.260 INCHES MAXIMUM IN |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 130.0 ALL LOCATIONS |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 3.052 INCHES MINIMUM AND 3.072 INCHES MAXIMUM IN |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 2.990 INCHES MINIMUM AND 3.010 INCHES MAXIMUM IN |
| Body Height | 2.678 INCHES MINIMUM AND 2.698 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Unthreaded Mounting Hole Diameter | 0.164 INCHES NOMINAL IN |
| Pole Quantity | 3 |
| Maximum Continuous Load Current Rating Per Pole | 70.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | INSTANTANEOUS ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 5000.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.190 INCHES IN |
| Body Length | 5.240 INCHES MINIMUM AND 5.260 INCHES MAXIMUM IN |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 0.990 INCHES MINIMUM AND 1.010 INCHES MAXIMUM IN |
| Inclosure Protection Type for Which Designed | DUSTPROOF AND FUNGUS PROOF AND HUMIDITY PROOF AND MOISTURE PROOF AND SHOCKPROOF AND VIBRATIONPROOF |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Terminal Type and Quantity | 6 THREADED STUD |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| P3X1163SMG4-70-208VAC | 5/9 Secondary reference Eaton Corp Heinemann Products Commercial Controls Div |
| 711599-115 | 3/2 Design control — primary reference U.S. Government activity |
NSN 5925-00-810-2107 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-00-810-2107: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 208.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 4 THREADED HOLE(S) AND 4 UNTHREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.