The Circuit Breaker, cataloged under National Stock Number 5925-00-752-8292, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 22 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-752-8292 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | AUTOMATIC |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Operating Voltage Type and Rating Per Pole in Volts | 30.0 AC AND 30.0 DC SINGLE LOCATION |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S) |
| Frequency in Hertz | 60.0 SINGLE LOCATION |
| Body Style | RECTANGULAR DIMENSIONAL ENVELOPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 115.0 SINGLE LOCATION |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Pole Quantity | 1 |
| Maximum Continuous Load Current Rating Per Pole | 50.0 AMPERES AC AND 50.0 AMPERES DC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1200.0 AC AND 1200.0 DC SINGLE LOCATION |
| Nominal Thread Size | 0.190 INCHES IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 3600.000 NOMINAL AT 125 PCT AND 30.000 NOMINAL AT 200 PCT SINGLE LOCATION |
| Inclosure Protection Type for Which Designed | WATERTIGHT |
| Test Data Document | 81349-MIL-C-13516 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.). |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Trip Release Ambient Temp Rating | 25.0 CELSIUS MAXIMUM SINGLE LOCATION DEGC |
| Terminal Type and Quantity | 2 THREADED STUD |
| Thread Series Designator | UNIFIED NATIONAL COARSE (UNC) |
| Trip Release Method | THERMAL SINGLE LOCATION |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| MILC13516TYPE2GRADEACLASS2 | 4/1 Identification reference U.S. Government activity |
NSN 5925-00-752-8292 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-00-752-8292: Reset Method: AUTOMATIC; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 30.0 AC AND 30.0 DC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 22 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.