PartsTable TECHNICAL DATA SHEET
NSN 5925-00-549-5360Government record, cited

Circuit Breaker5925-00-549-5360

NSN 5925-00-549-5360 · NIIN 005495360 · Part number ETN1075
L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc. · FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components · CAGE 30086
Government record, cited
NSN 5925-00-549-5360 — this item is cataloged by the U.S. Government under National Stock Number 5925-00-549-5360. Manufacturer of record part number: ETN1075.
Also searched as  5925-00-549-5360 · 5925005495360 · NIIN 005495360 · 00-549-5360 · FSC 5925 Circuit Breakers · CAGE 30086 · ETN1075 · 409737-6 · TN1130 · 5925PL1379239 · 454D507G06
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC AND 125.0 DC SINGLE LOCATION
  • Mounting Facility Type and Quantity: 1 TERMINAL AND 1 CLIP
  • Actuator Position Designation: AT POLE ONE
  • Frequency in Hertz: 400.0 SINGLE LOCATION
  • Fragility Factor: MODERATELY RUGGED
  • Body Style: SINGLE POLE TYPE
Identification
  • NSN: 5925-00-549-5360
  • NIIN: 005495360
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
  • Primary part number: ETN1075
  • Manufacturer: L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-549-5360, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 2 manufacturer part numbers for this item, enabling identification through both NSN and commercial part number lookups. 4 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-549-5360
Primary Part NumberETN1075
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
ManufacturerL3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.
StatusACTIVE
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts120.0 AC AND 125.0 DC SINGLE LOCATION
Mounting Facility Type and Quantity1 TERMINAL AND 1 CLIP
Actuator Position DesignationAT POLE ONE
Frequency in Hertz400.0 SINGLE LOCATION
Fragility FactorMODERATELY RUGGED
Body StyleSINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent138.0 SINGLE LOCATION
Precious MaterialSILVER
Circuit Protection TypeOVERCURRENT SINGLE LOCATION
Body Width0.969 INCHES NOMINAL IN
Body Height2.313 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Pole Quantity1
Maximum Continuous Load Current Rating Per Pole30.0 AMPERES AC SINGLE LOCATION
Trip Release CharacteristicTIME DELAY SINGLE LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC AND 2500.0 DC SINGLE LOCATION
Body Length3.500 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current10.000 MINIMUM AT 200 PCT AND 210.000 MAXIMUM AT 200 PCT SINGLE LOCATION
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedVIBRATION RESISTANT AND SHOCK RESISTANT
Precious Material and LocationCONTACT SURFACES SILVER
Test Data Document81349-MIL-C-17588 SPECIFICATION (INCLUDES ENGINEERING TYPE BULLETINS, BROCHURES,ETC., THAT REFLECT SPECIFICATION TYPE DATA IN SPECIFICATION FORMAT; EXCLUDES COMMERCIAL CATALOGS, INDUSTRY DIRECTORIES, AND SIMILAR TRADE PUBLICATIONS, REFLECTING GENERAL TYPE DATA ON CERTAIN ENVIRONMENTAL AND PERFORMANCE REQUIREMENTS AND TEST CONDITIONS THAT ARE SHOWN AS "TYPICAL", "AVERAGE", "NOMINAL", ETC.).
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Trip Release Ambient Temp Rating50.0 CELSIUS NOMINAL SINGLE LOCATION DEGC
Terminal Type and Quantity1 COMPRESSION AND 1 QUICK DISCONNECT, FEMALE
Special Handling FeatureMAGNETIC
Main Contact Tripping Mechanism TypeTRIP FREE
Boss Height0.188 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
Part NumberManufacturer
ETN1075 L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc. (USA)
TN1130 General Electric Co Electrical Distribution and Control (USA)
Reference documents
ReferenceMeaning
409737-6 5/2 Secondary reference
U.S. Government activity
5925PL1379239 6/9 Informative reference only
Jednolity Indeks Materialowy - Uniform Material Index
454D507G06 5/2 Secondary reference
U.S. Government activity
S6205-3232365REVCCLASSALB1-30AMP 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-00-549-5360?

NSN 5925-00-549-5360 is a Circuit Breaker, manufactured by L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc., classified under FSC 5925, Circuit Breakers. Status: active.

What part numbers are listed for NSN 5925-00-549-5360?

NSN 5925-00-549-5360 has 2 manufacturer part numbers on file: ETN1075 (L3harris Maritime Power & Energy Solutions, Inc. Dba Spd Electrical Systems, Inc.), TN1130 (General Electric Co Electrical Distribution and Control).

What are the specifications of ETN1075?

Key specifications for ETN1075: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC AND 125.0 DC SINGLE LOCATION; Mounting Facility Type and Quantity: 1 TERMINAL AND 1 CLIP; Actuator Position Designation: AT POLE ONE. 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-00-549-5360 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com