The Circuit Breaker, cataloged under National Stock Number 5925-00-434-4175, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 29 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-434-4175 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Operating Voltage Type and Rating Per Pole in Volts | 277.0 AC SINGLE LOCATION |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S) |
| Actuator Position Designation | AT POLE ONE |
| Ultimate Trip Time Per Pole in Seconds | 6.003 MINIMUM AND 0.040 MAXIMUM SINGLE LOCATION |
| Frequency in Hertz | 60.0 SINGLE LOCATION |
| Body Style | SINGLE POLE TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 1000.0 SINGLE LOCATION |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 1.660 INCHES NOMINAL IN |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Body Width | 0.750 INCHES NOMINAL IN |
| Pole Quantity | 1 |
| Mounting Surface to Terminal End Distance | 2.000 INCHES MAXIMUM IN |
| Maximum Continuous Load Current Rating Per Pole | 5.0 AMPERES AC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC SINGLE LOCATION |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 2.000 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.700 MINIMUM AT 125 PCT AND 12.000 MAXIMUM AT 125 PCT AND 0.350 MINIMUM AT 150 PCT AND 4.000 MAXIMUM AT 150 PCT AND 0.130 MINIMUM AT 200 PCT AND 1.300 MAXIMUM AT 200 PCT AND 0.030 MINIMUM AT 400 PCT AND 0.220 MAXIMUM AT 400 PCT AND 0.003 MINIMUM AT 1000 PCT AND 0.040 MAXIMUM AT 1000 PCT AND 0.008 MINIMUM AT 600 PCT AND 0.130 MAXIMUM AT 600 PCT AND 0.003 MINIMUM AT 800 PCT AND 0.070 MAXIMUM AT 800 PCT SINGLE LOCATION |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Inclosure Protection Type for Which Designed | MOISTURE RESISTANT AND VIBRATIONPROOF AND SALT SPRAY PROOF AND ICE RESISTANT |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Terminal Type and Quantity | 2 TAB, SOLDER LUG |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Thread Series Designator | UNIFIED NATIONAL COARSE (UNC) |
| Trip Release Method | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| Center to Center Distance Between Terminals Parallel to Length | 1.530 INCHES NOMINAL IN |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| UPG1-1-6-1-502-01 | 3/2 Design control — primary reference U.S. Government activity |
| UPG1-1-6-1-502-01 | 5/9 Secondary reference U.S. Government activity |
NSN 5925-00-434-4175 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-00-434-4175: Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 277.0 AC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 THREADED HOLE(S). 29 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.