PartsTable TECHNICAL DATA SHEET
NSN 5925-00-359-3943Government record, cited

Circuit Breaker5925-00-359-3943

NSN 5925-00-359-3943 · NIIN 003593943
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-00-359-3943 · 5925003593943 · NIIN 003593943 · 00-359-3943 · FSC 5925 Circuit Breakers · EB2070 · 4990D03G26 · S4990D03G26
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Bushing Length: 0.125 INCHES NOMINAL IN
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 250.0 DC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S)
  • Actuator Position Designation: AT POLE TWO
  • Frequency in Hertz: 60.0 ALL LOCATIONS
  • Unpackaged Unit Weight: 3.000 POUNDS NOMINAL LBS
Identification
  • NSN: 5925-00-359-3943
  • NIIN: 003593943
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-359-3943, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-359-3943
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Bushing Length0.125 INCHES NOMINAL IN
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts240.0 AC AND 250.0 DC ALL LOCATIONS
Mounting Facility Type and Quantity2 UNTHREADED HOLE(S)
Actuator Position DesignationAT POLE TWO
Frequency in Hertz60.0 ALL LOCATIONS
Unpackaged Unit Weight3.000 POUNDS NOMINAL LBS
Center to Center Distance Between Terminals Parallel to Width1.375 INCHES NOMINAL IN
Fragility FactorMODERATELY RUGGED
Body StyleMULTIPOLE-MULTIPLE ACTUATOR TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Distance Between Centerlines of Mounting Facilities Parallel to Body Length4.500 INCHES NOMINAL IN
Arc Quenching MethodMAGNETIC BLOWOUT
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Body Width2.750 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSE
Unthreaded Mounting Hole Diameter0.188 INCHES NOMINAL IN
Pole Quantity2
Mounting Surface to Terminal End Distance3.375 INCHES NOMINAL IN
Maximum Continuous Load Current Rating Per Pole70.0 AMPERES AC AND 70.0 AMPERES DC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps10000.0 AC AND 5000.0 DC ALL LOCATIONS
Body Length6.000 INCHES NOMINAL IN
Trip Delay Time in Seconds Per Rated Continuous Current55.000 MINIMUM AT 200 PCT AND 120.000 MAXIMUM AT 200 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedDUSTPROOF AND GENERAL PURPOSE AND FUNGUS RESISTANT
MaterialPLASTIC CASE
Actuator FunctionTRIP-RESET
Trip Release Ambient Temp Rating40.0 CELSIUS NOMINAL ALL LOCATIONS DEGC
Terminal Type and Quantity4 COMPRESSION
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
EB2070 3/2 Design control — primary reference
U.S. Government activity
4990D03G26 5/2 Secondary reference
U.S. Government activity
S4990D03G26 5/9 Secondary reference
U.S. Government activity

Frequently Asked Questions

What is NSN 5925-00-359-3943?

NSN 5925-00-359-3943 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-00-359-3943?

Key specifications for 5925-00-359-3943: Bushing Length: 0.125 INCHES NOMINAL IN; Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 240.0 AC AND 250.0 DC ALL LOCATIONS; Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S). 30 specifications are documented in the U.S. Government catalog.

Is NSN 5925-00-359-3943 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com