The Circuit Breaker, cataloged under National Stock Number 5925-00-283-6501, is classified within Federal Supply Class 5925 (No Item Name Available) of the Electrical and Electronic Equipment Components group. The primary manufacturer of record is Eaton Corp Heinemann Products Commercial Controls Div. Government technical data includes 30 verified specifications, sourced from the Federal Logistics Information System (FLIS). This item has 1 commercial cross-reference from 1 manufacturer, enabling identification through both NSN and commercial part number lookups. 4 verified substitutes exist in the FLIS interchangeability database. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-283-6501 |
| Primary Part Number | AM12 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — No Item Name Available |
| Manufacturer | Eaton Corp Heinemann Products Commercial Controls Div |
| Status | ACTIVE |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Maximum Continuous Load Current Rating Per Pole | 20.0 AMPERES AC SINGLE LOCATION |
| Thread Series Designator | UNIFIED NATIONAL COARSE (UNC) |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 2000.0 AC SINGLE LOCATION |
| Terminal Type and Quantity | 2 THREADED STUD |
| Reset Method | MANUAL |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Actuator Position Designation | AT POLE ONE |
| Material | PLASTIC CASE |
| Fragility Factor | MODERATELY RUGGED |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 SINGLE LOCATION |
| Mounting Surface to Terminal End Distance | 2.611 INCHES NOMINAL IN |
| Boss Height | 0.140 INCHES NOMINAL IN |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 2.062 INCHES NOMINAL IN |
| Mounting Facility Type and Quantity | 2 THREADED HOLE(S) |
| Pole Quantity | 1 |
| Thread Quantity Per Inch | 32 |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Special Handling Feature | MAGNETIC |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Center to Center Distance Between Terminals Parallel to Length | 1.938 INCHES NOMINAL IN |
| Body Length | 2.500 INCHES NOMINAL IN |
| Body Width | 0.750 INCHES NOMINAL IN |
| Operating Voltage Type and Rating Per Pole in Volts | 125.0 AC SINGLE LOCATION |
| Trip Delay Time in Seconds Per Rated Continuous Current | 3.800 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT SINGLE LOCATION |
| Trip Release Method | MAGNETIC-HYDRAULIC SINGLE LOCATION |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Nominal Thread Size | 0.138 INCHES IN |
| Actuator Function | TRIP-RESET |
| Acquisition Status | ACTIVE |
| HAZMAT | No |
| Part Number | Manufacturer |
|---|---|
| AM12 | Eaton Corp Heinemann Products Commercial Controls Div (USA) |
NSN 5925-00-283-6501 is a Circuit Breaker, manufactured by Eaton Corp Heinemann Products Commercial Controls Div, classified under FSC 5925 (No Item Name Available). Status: active.
NSN 5925-00-283-6501 has 1 cross-referenced part number: AM12 (Eaton Corp Heinemann Products Commercial Controls Div).
There are 4 known substitutes for 5925-00-283-6501: 5925-00-068-0740, 4730-00-369-4595, 5925-00-572-4982 and 1 more. Verify interchangeability with system specifications before substitution.
Key specifications for AM12: Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Maximum Continuous Load Current Rating Per Pole: 20.0 AMPERES AC SINGLE LOCATION; Thread Series Designator: UNIFIED NATIONAL COARSE (UNC); Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps: 2000.0 AC SINGLE LOCATION. 30 total characteristics are documented in the Federal Logistics Information System.