The Circuit Breaker, cataloged under National Stock Number 5925-00-279-6733, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 19 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 2 items share a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-279-6733 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Reset Method | MANUAL |
| Operating Voltage Type and Rating Per Pole in Volts | 120.0 AC AND 120.0 DC ALL LOCATIONS |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 115.0 ALL LOCATIONS |
| Arc Quenching Method | AIR |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Pole Quantity | 3 |
| Maximum Continuous Load Current Rating Per Pole | 25.0 AMPERES AC AND 25.0 AMPERES DC ALL LOCATIONS |
| Trip Release Characteristic | INSTANTANEOUS AND TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 5000.0 AC AND 5000.0 DC ALL LOCATIONS |
| Trip Delay Time in Seconds Per Rated Continuous Current | 10.000 MINIMUM AT 200 PCT AND 100.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 1 TOGGLE |
| Inclosure Protection Type for Which Designed | SHOCKPROOF |
| Material | PLASTIC CASE |
| Actuator Function | RESET |
| Trip Release Ambient Temp Rating | 50.0 CELSIUS NOMINAL ALL LOCATIONS DEGC |
| Terminal Type and Quantity | 6 PIN |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Trip Release Method | MAGNETIC ALL LOCATIONS |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| MILC17588TYPEALB5 | 4/1 Identification reference U.S. Government activity |
| ALB5 | 4/1 Identification reference U.S. Government activity |
NSN 5925-00-279-6733 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
2 possible matches (shared part number, not a government interchangeability claim): 5925-00-279-6734, 5925-00-279-6757. Verify interchangeability with system specifications before substitution.
Key specifications for 5925-00-279-6733: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC AND 120.0 DC ALL LOCATIONS; Overall Height: 4.125 INCHES NOMINAL IN; Frequency in Hertz: 60.0 ALL LOCATIONS. 19 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.