PartsTable TECHNICAL DATA SHEET
NSN 5925-00-272-7002Government record, cited

Circuit Breaker5925-00-272-7002

NSN 5925-00-272-7002 · NIIN 002727002
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-00-272-7002 · 5925002727002 · NIIN 002727002 · 00-272-7002 · FSC 5925 Circuit Breakers · PLMS105 · PDLMS105
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUALMANUAL
  • Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION
  • Operating Voltage Type and Rating Per Pole in Volts: 30.0 DC SINGLE LOCATION30.0 DC SINGLE LOCATION
  • Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S)2 UNTHREADED HOLE(S)
  • Actuator Position Designation: AT POLE ONEAT POLE ONE
  • Body Style: SINGLE POLE TYPESINGLE POLE TYPE
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 125.0 SINGLE LOCATION125.0 SINGLE LOCATION
Identification
  • NSN: 5925-00-272-7002
  • NIIN: 002727002
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-272-7002, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 27 specifications, cited from the U.S. Government catalog. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-272-7002
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUALMANUAL
Internal Trip Release ConfigurationSERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION
Operating Voltage Type and Rating Per Pole in Volts30.0 DC SINGLE LOCATION30.0 DC SINGLE LOCATION
Mounting Facility Type and Quantity2 UNTHREADED HOLE(S)2 UNTHREADED HOLE(S)
Actuator Position DesignationAT POLE ONEAT POLE ONE
Body StyleSINGLE POLE TYPESINGLE POLE TYPE
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 SINGLE LOCATION125.0 SINGLE LOCATION
Distance Between Centerlines of Mounting Facilities Parallel to Body Length2.406 INCHES NOMINAL2.406 INCHES NOMINAL IN
Circuit Protection TypeOVERCURRENT SINGLE LOCATIONOVERCURRENT SINGLE LOCATION
Body Width1.875 INCHES NOMINAL1.875 INCHES NOMINAL IN
Storage TypeGENERAL PURPOSE WAREHOUSEGENERAL PURPOSE WAREHOUSE
Unthreaded Mounting Hole Diameter0.250 INCHES NOMINAL0.250 INCHES NOMINAL IN
Pole Quantity11
Mounting Surface to Terminal End Distance1.640 INCHES NOMINAL1.640 INCHES NOMINAL IN
Maximum Continuous Load Current Rating Per Pole105.0 AMPERES DC SINGLE LOCATION105.0 AMPERES DC SINGLE LOCATION
Trip Release CharacteristicTIME DELAY SINGLE LOCATIONTIME DELAY SINGLE LOCATION
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps575.0 DC SINGLE LOCATION575.0 DC SINGLE LOCATION
Trip Delay Time in Seconds Per Rated Continuous Current15.000 MINIMUM AT 200 PCT AND 15.000 MINIMUM AT 200 PCT AND 50.000 MAXIMUM AT 200 PCT SINGLE LOCATION50.000 MAXIMUM AT 200 PCT SINGLE LOCATION
Manual Actuator Type and Quantity1 PUSH BUTTON1 PUSH BUTTON
Inclosure Protection Type for Which DesignedDUSTPROOF AND DUSTPROOF AND WEATHERPROOFWEATHERPROOF
MaterialPLASTIC CASE
Actuator FunctionRESETRESET
Trip Release Ambient Temp Rating25.0 CELSIUS NOMINAL SINGLE LOCATION25.0 CELSIUS NOMINAL SINGLE LOCATION DEGC
Terminal Type and Quantity2 THREADED STUD2 THREADED STUD
Main Contact Tripping Mechanism TypeTRIP FREETRIP FREE
Trip Release MethodTHERMAL SINGLE LOCATIONTHERMAL SINGLE LOCATION
Center to Center Distance Between Terminals Parallel to Length1.062 INCHES NOMINAL1.062 INCHES NOMINAL IN
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
PLMS105 5/9 Secondary reference
U.S. Government activity
PDLMS105 3/2 Design control — primary reference
U.S. Government activity
No interchangeability data on file.
Other items in FSC 5925 — Circuit Breakers
Items in the same Federal Supply class. No interchangeability or substitution relationship is implied.
5925-00-001-1277
CIRCUIT BREAKER
5925-00-001-2809
5925-00-001-2809 · Item name not on file
5925-00-001-3838
CIRCUIT BREAKER
5925-00-001-5748
5925-00-001-5748 · Item name not on file
5925-00-001-5926
5925-00-001-5926 · Item name not on file
5925-00-001-5938
5925-00-001-5938 · Item name not on file
5925-00-001-5942
CIRCUIT BREAKER
5925-00-001-5977
CIRCUIT BREAKER

Frequently Asked Questions

What is NSN 5925-00-272-7002?

NSN 5925-00-272-7002 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What are the specifications of 5925-00-272-7002?

Key specifications for 5925-00-272-7002: Reset Method: MANUALMANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATIONSERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 30.0 DC SINGLE LOCATION30.0 DC SINGLE LOCATION; Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S)2 UNTHREADED HOLE(S). 27 specifications are documented in the U.S. Government catalog.

Is NSN 5925-00-272-7002 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.