The Circuit Breaker, cataloged under National Stock Number 5925-00-256-1218, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. The manufacturer of record is L3harris Technologies, Inc. Dba Harris Corp Div Antenna Products. Government technical data includes 30 specifications, cited from the U.S. Government catalog. The record lists 1 manufacturer part number for this item, enabling identification through both NSN and commercial part number lookups. 2 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 1 item shares a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-256-1218 |
| Primary Part Number | 368477-1 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Manufacturer | L3harris Technologies, Inc. Dba Harris Corp Div Antenna Products |
| Status | ACTIVE |
| Bushing Length | 0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM IN |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP ALL LOCATIONS |
| Operating Voltage Type and Rating Per Pole in Volts | 250.0 AC ALL LOCATIONS |
| Mounting Facility Type and Quantity | 4 THREADED HOLE(S) |
| Actuator Position Designation | AT EACH POLE |
| Frequency in Hertz | 60.0 ALL LOCATIONS |
| Center to Center Distance Between Terminals Parallel to Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM IN |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | MULTIPOLE-MULTIPLE ACTUATOR TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 125.0 ALL LOCATIONS |
| External Actuator Linkage Arrangement | ONE AND TWO LINKED |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Length | 1.802 INCHES MINIMUM AND 1.822 INCHES MAXIMUM IN |
| Arc Quenching Method | MAGNETIC BLOWOUT |
| Circuit Protection Type | OVERCURRENT ALL LOCATIONS |
| Body Width | 1.510 INCHES MINIMUM AND 1.530 INCHES MAXIMUM IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 2 |
| Mounting Surface to Terminal End Distance | 1.990 INCHES MINIMUM AND 2.010 INCHES MAXIMUM IN |
| Maximum Continuous Load Current Rating Per Pole | 30.0 AMPERES AC ALL LOCATIONS |
| Trip Release Characteristic | TIME DELAY ALL LOCATIONS |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC ALL LOCATIONS |
| Nominal Thread Size | 0.138 INCHES IN |
| Body Length | 2.490 INCHES MINIMUM AND 2.510 INCHES MAXIMUM IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 2.800 MINIMUM AT 200 PCT AND 8.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| Manual Actuator Type and Quantity | 2 TOGGLE |
| Distance Between Centerlines of Mounting Facilities Parallel to Body Width | 0.740 INCHES MINIMUM AND 0.760 INCHES MAXIMUM IN |
| Inclosure Protection Type for Which Designed | DUSTPROOF AND FUNGUS PROOF |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Part Number | Manufacturer |
|---|---|
| 368477-1 PRIMARY | L3harris Technologies, Inc. Dba Harris Corp Div Antenna Products (USA) |
| Reference | Meaning |
|---|---|
| DMS 83059B | 5/9 Secondary reference Dla Land and Maritime Dba Engineering and Technical Support Div Document Standardization Division (vendor Item Drawings) |
| 2XAM17-30-250-60-55 | 5/9 Secondary reference Eaton Corp Heinemann Products Commercial Controls Div |
NSN 5925-00-256-1218 is a Circuit Breaker, manufactured by L3harris Technologies, Inc. Dba Harris Corp Div Antenna Products, classified under FSC 5925, Circuit Breakers. Status: active.
NSN 5925-00-256-1218 has 1 manufacturer part number on file: 368477-1 (L3harris Technologies, Inc. Dba Harris Corp Div Antenna Products).
1 possible match (shared part number, not a government interchangeability claim): 5950-00-466-1398. Verify interchangeability with system specifications before substitution.
Key specifications for 368477-1: Bushing Length: 0.146 INCHES MINIMUM AND 0.166 INCHES MAXIMUM IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP ALL LOCATIONS; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS. 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.