The Circuit Breaker, cataloged under National Stock Number 5925-00-252-4060, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 30 specifications, cited from the U.S. Government catalog. 1 additional reference document (drawings, advisory and superseded references) is recorded in the U.S. Government catalog. Current acquisition status: Active.
| Parameter | Value |
|---|---|
| NSN | 5925-00-252-4060 |
| Item Name | Circuit Breaker |
| FSC / FSG | 5925 / 59 — Circuit Breakers |
| Status | ACTIVE |
| Bushing Length | 0.250 INCHES NOMINAL IN |
| Reset Method | MANUAL |
| Internal Trip Release Configuration | SERIES TRIP SINGLE LOCATION |
| Operating Voltage Type and Rating Per Pole in Volts | 120.0 AC SINGLE LOCATION |
| Mounting Facility Type and Quantity | 1 THREADED BUSHING |
| Actuator Position Designation | AT POLE ONE |
| Frequency in Hertz | 60.0 SINGLE LOCATION |
| Unpackaged Unit Weight | 2.000 OUNCES NOMINAL OZ |
| Fragility Factor | MODERATELY RUGGED |
| Body Style | SINGLE POLE TYPE |
| Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent | 135.0 SINGLE LOCATION |
| Circuit Protection Type | OVERCURRENT SINGLE LOCATION |
| Body Width | 0.656 INCHES NOMINAL IN |
| Storage Type | GENERAL PURPOSE WAREHOUSE |
| Pole Quantity | 1 |
| Mounting Surface to Terminal End Distance | 1.669 INCHES NOMINAL IN |
| Maximum Continuous Load Current Rating Per Pole | 1.0 AMPERES AC SINGLE LOCATION |
| Trip Release Characteristic | TIME DELAY SINGLE LOCATION |
| Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps | 1000.0 AC SINGLE LOCATION |
| Nominal Thread Size | 0.469 INCHES IN |
| Body Length | 1.781 INCHES NOMINAL IN |
| Trip Delay Time in Seconds Per Rated Continuous Current | 0.100 MINIMUM AT 200 PCT AND 1.500 MAXIMUM AT 200 PCT SINGLE LOCATION |
| Manual Actuator Type and Quantity | 1 PUSH-PULL |
| Inclosure Protection Type for Which Designed | FUNGUS RESISTANT |
| Thread Quantity Per Inch | 32 |
| Material | PLASTIC CASE |
| Actuator Function | TRIP-RESET |
| Terminal Type and Quantity | 2 TAB W/SCREW |
| Special Handling Feature | MAGNETIC |
| Main Contact Tripping Mechanism Type | TRIP FREE |
| Acquisition Status | ACTIVE |
| DEMIL Code | DEMIL A — No Demilitarization Required |
| Hazard | Possible hazard — SDS may be required (DLA HMIC P) |
| Criticality Code | X |
| Reference | Meaning |
|---|---|
| 3MC1-101-1 | 3/2 Design control — primary reference U.S. Government activity |
NSN 5925-00-252-4060 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.
Key specifications for 5925-00-252-4060: Bushing Length: 0.250 INCHES NOMINAL IN; Reset Method: MANUAL; Internal Trip Release Configuration: SERIES TRIP SINGLE LOCATION; Operating Voltage Type and Rating Per Pole in Volts: 120.0 AC SINGLE LOCATION. 30 specifications are documented in the U.S. Government catalog.
Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.
U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.