PartsTable TECHNICAL DATA SHEET
NSN 5925-00-201-7130Government record, cited

Circuit Breaker5925-00-201-7130

NSN 5925-00-201-7130 · NIIN 002017130
FSC 5925 — Circuit Breakers · FSG 59 — Electrical and Electronic Equipment Components
Government record, cited
Also searched as  5925-00-201-7130 · 5925002017130 · NIIN 002017130 · 00-201-7130 · FSC 5925 Circuit Breakers · 320P112 · SPEC61-362M7-60A · 320-112
Nearby stock numbers  ·
Features
  • Circuit Breaker — FSC 5925
  • Reset Method: MANUAL
  • Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS
  • Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S)
  • Ultimate Trip Time Per Pole in Seconds: 160.000 MINIMUM AND 600.000 MAXIMUM ALL LOCATIONS
  • Frequency in Hertz: 60.0 ALL LOCATIONS
  • Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent: 125.0 ALL LOCATIONS
  • Circuit Protection Type: OVERCURRENT ALL LOCATIONS
Identification
  • NSN: 5925-00-201-7130
  • NIIN: 002017130
  • FSC: 5925 — Circuit Breakers
  • FSG: 59 — Electrical and Electronic Equipment Components
General Description

The Circuit Breaker, cataloged under National Stock Number 5925-00-201-7130, is classified within Federal Supply Class 5925 (Circuit Breakers) of the Electrical and Electronic Equipment Components group. Government technical data includes 19 specifications, cited from the U.S. Government catalog. 3 additional reference documents (drawings, advisory and superseded references) are recorded in the U.S. Government catalog. 2 items share a part number with this NSN in the catalog (possible match — not a government interchangeability claim). Current acquisition status: Active.

Technical Specifications
ParameterValue
NSN5925-00-201-7130
Item NameCircuit Breaker
FSC / FSG5925 / 59 — Circuit Breakers
StatusACTIVE
Reset MethodMANUAL
Operating Voltage Type and Rating Per Pole in Volts250.0 AC ALL LOCATIONS
Mounting Facility Type and Quantity2 UNTHREADED HOLE(S)
Ultimate Trip Time Per Pole in Seconds160.000 MINIMUM AND 600.000 MAXIMUM ALL LOCATIONS
Frequency in Hertz60.0 ALL LOCATIONS
Ultimate Trip Rating of Continuous Current Rating Per Pole in Percent125.0 ALL LOCATIONS
Circuit Protection TypeOVERCURRENT ALL LOCATIONS
Pole Quantity2
Maximum Continuous Load Current Rating Per Pole60.0 AMPERES AC ALL LOCATIONS
Trip Release CharacteristicTIME DELAY ALL LOCATIONS
Maximum Interrupting Capacity Current Type and Rating Per Pole in Amps5000.0 AC ALL LOCATIONS
Trip Delay Time in Seconds Per Rated Continuous Current40.000 MINIMUM AT 200 PCT AND 125.000 MAXIMUM AT 200 PCT AND 12.000 MINIMUM AT 300 PCT AND 38.000 MAXIMUM AT 300 PCT ALL LOCATIONS
Manual Actuator Type and Quantity1 TOGGLE
Inclosure Protection Type for Which DesignedFUNGUS RESISTANT AND MOISTURE RESISTANT
MaterialPLASTIC CASE
Actuator FunctionRESET
Terminal Type and Quantity4 SCREW
Main Contact Tripping Mechanism TypeTRIP FREE
Trip Release MethodMAGNETIC ALL LOCATIONS
Lifecycle & Compliance
Acquisition StatusACTIVE
DEMIL CodeDEMIL A — No Demilitarization Required
HazardPossible hazard — SDS may be required (DLA HMIC P)
Criticality CodeX
⇄ Related Items 2
Each row states its source: a government interchangeability/replacement code, or a possible match on a shared part number.
4820-00-482-89033201-12 POSSIBLE MATCH
VALVE,SINGLE SPOOL
Possible match (shared part number)Husco International Inc
4920-01-585-41473201-1-2 POSSIBLE MATCH
ATTENUATOR,PRO
Possible match (shared part number)Spectrum Control Inc Div Weinschel
Cross-Reference Index
No manufacturer part numbers on file in the U.S. Government catalog.
Reference documents
ReferenceMeaning
320P112 5/9 Secondary reference
Cummins Power Generation Inc.
SPEC61-362M7-60A 3/9 Design control — primary reference
Eaton Corp Heinemann Products Commercial Controls Div
320-112 5/9 Secondary reference
Cummins Power Generation Inc.
Related Parts
4820-00-482-8903POSSIBLE MATCH
VALVE,SINGLE SPOOL
3201-12
4920-01-585-4147POSSIBLE MATCH
ATTENUATOR,PRO
3201-1-2

Frequently Asked Questions

What is NSN 5925-00-201-7130?

NSN 5925-00-201-7130 is a Circuit Breaker, classified under FSC 5925, Circuit Breakers. Status: active.

What NSN replaces 5925-00-201-7130?

2 possible matches (shared part number, not a government interchangeability claim): 4820-00-482-8903, 4920-01-585-4147. Verify interchangeability with system specifications before substitution.

What are the specifications of 5925-00-201-7130?

Key specifications for 5925-00-201-7130: Reset Method: MANUAL; Operating Voltage Type and Rating Per Pole in Volts: 250.0 AC ALL LOCATIONS; Mounting Facility Type and Quantity: 2 UNTHREADED HOLE(S); Ultimate Trip Time Per Pole in Seconds: 160.000 MINIMUM AND 600.000 MAXIMUM ALL LOCATIONS. 19 specifications are documented in the U.S. Government catalog.

Is NSN 5925-00-201-7130 hazardous material?

Possible hazard — SDS may be required (DLA HMIC P). Hazard information on this page is shown exactly as it appears in the DLA record.

Sources

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-16.

U.S. Government catalog: edition PUBLOGDVD v12.0.0 (OCT 2026), edition date 2026-10-01, retrieved 2026-10-18.

✓ Data cited from the U.S. Government catalog; commercial cross-references from OEM and certified industry sources.
PartsTable Design LLC · partstable.com