The CIRCUIT BREAKER is a the manufacturer industrial component. Key specifications include material: PLASTIC CASE, body_style: MULTIPOLE-SINGLE ACTUATOR TYPE, body_width: 45.0 MILLIMETERS NOMINAL MM, body_height: 38.0 MILLIMETERS NOMINAL MM, body_length: 19.5 MILLIMETERS NOMINAL MM, reset_method: MANUAL. This product is currently in active production with full OEM support.
This part is cataloged in the Federal Logistics Information System (FLIS) under NSN 5925-01-523-1917, indicating validated use in U.S. government and defense logistics supply chains. Available through authorized enterprise resellers and TPM (Third Party Maintenance) channels.
Verify compatibility with your specific system configuration before ordering.
| material | PLASTIC CASE |
| body_style | MULTIPOLE-SINGLE ACTUATOR TYPE |
| body_width | 45.0 MILLIMETERS NOMINAL MM |
| body_height | 38.0 MILLIMETERS NOMINAL MM |
| body_length | 19.5 MILLIMETERS NOMINAL MM |
| reset_method | MANUAL |
| pole_quantity | 3 |
| bushing_length | 6.5 MILLIMETERS NOMINAL MM |
| special_features | BLACK PUSH BUTTON |
| actuator_function | TRIP-RESET |
| frequency_in_hertz | 400.0 ALL LOCATIONS |
| nominal_thread_size | 12.0 MILLIMETERS MM |
| NSN | 5925-01-523-1917 |
| TRIP DELAY TIME IN SECONDS PER RATED CONTINUOUS CURRENT | 2.000 MINIMUM AT 200 PCT AND 10.000 MAXIMUM AT 200 PCT ALL LOCATIONS |
| TRIP RELEASE CHARACTERISTIC | TIME DELAY ALL LOCATIONS |
| TERMINAL TYPE AND QUANTITY | 6 SCREW |
| FREQUENCY IN HERTZ | 400.0 ALL LOCATIONS |
| ACTUATOR FUNCTION | TRIP-RESET |
| MAXIMUM CONTINUOUS LOAD CURRENT RATING PER POLE | 5.0 AMPERES AC AND 5.0 AMPERES DC ALL LOCATIONS |
| THREAD SERIES DESIGNATOR | ISO M |
| SPECIAL FEATURES | BLACK PUSH BUTTON |
| RESET METHOD | MANUAL |
| TRIP RELEASE METHOD | THERMAL ALL LOCATIONS |